Instrumentation Signal · Free Calculator

NAMUR NE43 4 to 20 mA Signal Checker

Check a 4 to 20 mA loop current against the NAMUR NE43 signal levels: valid measurement, saturated over or under range, or a failure alarm. The matching percent and process value are shown.

NAMUR NE43Failure currentSaturation limitsBurnout detection
mA
eng. units
eng. units
FAILURE LOW (≤ 3.6 mA): treat as transmitter or loop fault
NE43 statusFAILURE LOW (≤ 3.6 mA): treat as transmitter or loop fault
Percent of span−3.125 %
Process value (if valid)not valid
Recommended DCS alarmfault alarm at ≤ 3.6 mA and ≥ 21 mA
How this result was calculated
  1. Measurement information: 3.8 to 20.5 mA
  2. Failure information: ≤ 3.6 mA or ≥ 21 mA
  3. % = (I − 4) ÷ 16 × 100 = −3.125 %
Advertisement

NAMUR NE43 Signal Levels

Valid measurement: 4 to 20 mA
Saturation (over and under range): 3.8 to 4 mA and 20 to 20.5 mA
Failure signal: ≤ 3.6 mA (low) or ≥ 21 mA (high)

NAMUR recommendation NE43 standardises the signal level for failure information of digital transmitters. The gap between 3.6 and 3.8 mA and between 20.5 and 21 mA separates a saturated measurement from a failure, so the control system can tell them apart. Whether a transmitter fails high or low is configured in the device.

Worked example

A loop reading 3.5 mA is a NE43 failure low signal: the transmitter has detected a fault (for example a broken sensor) and the DCS should raise a fault alarm, not show −3 % of range.

Key insight: set the DCS or PLC input to flag a fault at ≤ 3.6 mA and ≥ 21 mA, and choose fail high or fail low per loop so a failure drives the control action to the safe side.
Advertisement

Frequently Asked Questions

What is NAMUR NE43?

A NAMUR recommendation that defines separate current ranges for valid measurement and for failure signals on 4 to 20 mA transmitters.

Should a transmitter fail high or low?

It depends on the loop. Choose the direction that makes the controller or trip act safely, for example fail high on a high level trip.

Why not just use 0 mA for a failure?

A two wire transmitter needs some current to run itself, so it cannot output 0 mA. 3.6 mA is low enough to be clearly abnormal.