DP Level Transmitter Calibration Report Template

A 5 point calibration report for DP level transmitters, including elevated and suppressed zero ranges. It shows the equivalent level for each applied DP so technicians can relate the test to the tank.

Excel (.xlsx)Printable PDFFilled exampleFree, no sign up

Download

  • How to Use sheet with steps
  • Template sheet, blank and ready
  • Example sheet, filled in
  • 132 built in formulas
  • A4 landscape print setup
  • Works in Excel, Google Sheets and LibreOffice

Preview of the Filled Example

This is the Example sheet from the download, so you can see exactly how the completed dp level transmitter calibration report looks.

Tag numberLT 2101
ServiceCondensate drum level
LRV (mbar), negative for elevated zero−294.2
URV (mbar)0
Process specific gravity1
Low sideWet leg, water, 3 m
Tolerance (± % of span)0.25
Calibration date25 Oct 2026

Calibration results

Test point (% of span)Applied DP (mbar)Equivalent level (m)Expected output (mA)As found output (mA)As found error (% span)As found resultAs left output (mA)As left error (% span)As left result
0−294.200.0004.0004.0100.06PASS4.0010.01PASS
25−220.650.7508.0008.0210.13PASS8.0020.01PASS
50−147.101.50012.00012.0300.19PASS12.0010.01PASS
75−73.552.25016.00016.0410.26FAIL16.0010.01PASS
1000.003.00020.00020.0500.31FAIL20.0020.01PASS
75−73.552.25016.00016.0380.24PASS16.0020.01PASS
50−147.101.50012.00012.0270.17PASS12.0010.01PASS
25−220.650.7508.0008.0190.12PASS8.0010.01PASS
0−294.200.0004.0004.0080.05PASS4.0000.00PASS
Maximum as found error (% span):0.31  ·  Maximum as left error (% span):0.01  ·  Overall result (as left if adjusted, else as found):PASS
Advertisement

About the DP Level Transmitter Calibration Report

DP level transmitters often have elevated or suppressed zero ranges because of wet legs, seals and mounting height. Testing in DP while showing the equivalent level makes the calibration easier to check against the real tank.

How to fill in this template

  1. Enter LRV and URV in mbar as calculated for the tank, including wet leg or seal head.
  2. Enter process SG to see the equivalent level for each test point.
  3. Apply DP at the HP side (or apply vacuum to the LP side for negative values) and record outputs upscale and downscale.
  4. Adjust if needed and record as left readings.
  5. Restore wet legs and seals before returning to service.

What the formulas do

  • Applied DP = LRV + span × test point %.
  • Equivalent level (m) = (applied DP − LRV) × 100 ÷ (SG × 9806.65).
  • Error (% span) = (measured − expected mA) ÷ 16 × 100.

Related tools

Advertisement

Frequently Asked Questions

Why is my LRV negative?

A wet leg or seal capillary on the LP side adds head, so an empty tank gives negative DP.

Can I calibrate a level transmitter by filling the tank?

A wet calibration is possible but slow; bench or in situ DP calibration is normal, followed by a level check.

What is 1 m of water in mbar?

About 98.07 mbar.