PFH Calculator for High Demand Safety Functions

For safety functions demanded more than once a year or running continuously, IEC 61508 uses PFH, the average frequency of dangerous failure per hour. This calculator gives PFH and the SIL band for simple 1oo1 and 1oo2 architectures.

PFHHigh demand modeContinuous modeIEC 61508
%
h
h
per year
Simplified equations without diagnostic coverage. Use IEC 61508-6 or a verified SIL tool for final verification.
PFH5.00 × 10^−7 per hour
SIL band (high demand)SIL 2
Demand modeHigh demand (more than once a year): PFH applies
Dangerous failures per year0.00438
Mean time to dangerous failure228.3 years
How this result was calculated
  1. PFH ≈ λDU = 5.00 × 10^−7
  2. PFH = 5.00 × 10^−7 /h → SIL 2

IEC 61508 high demand / continuous mode

SILPFH (per hour)
4≥ 10⁻⁹ to < 10⁻⁸
3≥ 10⁻⁸ to < 10⁻⁷
2≥ 10⁻⁷ to < 10⁻⁶
1≥ 10⁻⁶ to < 10⁻⁵
Advertisement

PFH Equations (Simplified)

1oo1: PFH ≈ λDU
1oo2: PFH ≈ 2[(1 − β)λDU]² × tCE + β × λDU, tCE = T/2 + MRT

λDU is the dangerous undetected failure rate per channel, β the common cause factor, T the proof test interval and MRT the mean repair time. Detected failures are assumed to bring the process to a safe state. These are simplified forms of the IEC 61508-6 equations.

Worked example

A 1oo1 function with λDU = 5 × 10⁻⁷ /h has PFH = 5 × 10⁻⁷ /h, which is SIL 2 in high demand mode. As 1oo2 with β = 5 % and a yearly test, PFH ≈ 2.7 × 10⁻⁸ /h (SIL 3).

Key insight: in high demand mode, proof testing does little for a 1oo1 function because a dangerous failure is likely to meet a demand before the next test. Redundancy and diagnostics matter more.
Advertisement

Frequently Asked Questions

When is PFH used instead of PFDavg?

When the demand rate is higher than once per year or the function operates continuously, as defined in IEC 61508 and IEC 61511.

What is the unit of PFH?

Dangerous failures per hour, the average frequency of dangerous failure of the safety function.

Why is 1oo1 PFH equal to λDU?

In high demand each undetected dangerous failure is soon followed by a demand, so the failure rate becomes the hazard rate.