RTD and Thermocouple Tolerance Class Calculator
Find the maximum permitted deviation of a sensor at a given temperature for its tolerance class: IEC 60751 for platinum RTDs and IEC 60584-1 for thermocouples.
- IEC 60751: tolerance = a + b × |t| for each class
- All classes for this sensor are listed in the table below.
Tolerance at 200 °C
| Class | Valid range | Tolerance |
|---|---|---|
| AA (wire wound) | −50 to 250 °C | ± 0.44 °C |
| A (wire wound) | −100 to 450 °C | ± 0.55 °C |
| B (wire wound) | −196 to 600 °C | ± 1.3 °C |
| C (wire wound) | −196 to 600 °C | ± 2.6 °C |
| AA (film) | 0 to 150 °C | outside range |
| A (film) | −30 to 300 °C | ± 0.55 °C |
| B (film) | −50 to 500 °C | ± 1.3 °C |
Tolerance Class Formulas
Thermocouple K (IEC 60584-1): Class 1 ±1.5 °C or ±0.004|t|, Class 2 ±2.5 °C or ±0.0075|t|, whichever is greater
t is the temperature in °C. RTD classes apply over ranges that differ for wire wound and thin film elements. Thermocouple tolerances apply to the wire as supplied; they do not include drift, installation or instrument errors.
Worked example
At 200 °C a Class A RTD may deviate ±0.55 °C and Class B ±1.3 °C. A Class 1 type K thermocouple at 600 °C may deviate ±2.4 °C.
Frequently Asked Questions
What is the difference between Class A and Class B RTDs?
Class A has less than half the permitted error of Class B, ±(0.15 + 0.002|t|) against ±(0.3 + 0.005|t|), and a narrower valid range.
Which thermocouple class should I specify?
Class 1 for better accuracy where available; Class 2 is the standard grade. Class 3 covers sub zero temperatures for some types.
Do these tolerances include drift?
No. They are initial tolerances. Thermocouples in particular drift with time at high temperature.