Table of Contents
ToggleDP Transmitter Level Measurement
In this blog, we are going to study how DP transmitter level measurement is used for open tanks and closed tanks.
Differential pressure transmitter has 2 tapings.
HP (High Pressure) Taping
LP (Low Pressure) Taping
With the help of the above two tapings, we level measurement can be done.
Lets understand first, why we are using DP Transmitters for level measurements.
There are many physical level measuring instruments available in the market. DP Flow Transmitter is utilized due to the need for monitoring the level signal from a remote-control room, eliminating the need for physical visits to the tank for level observation.
How Is Level Measured with a DP Transmitter?
A DP transmitter measures level from hydrostatic head: ΔP = level × specific gravity (in mm of water column). In an open tank the HP side connects to the bottom and LP is vented; in a closed tank LP connects to the tank top through a dry leg (gas filled) or a wet leg (liquid filled). LRV is the DP at 0% level and URV the DP at 100%.
Example: 2000 mm span, SG 1.1, transmitter at the bottom tap. Open tank: LRV = 0, URV = 2200 mmH2O. With a 2500 mm wet leg of SG 1.0: LRV = 0 − 2500 = −2500 mmH2O and URV = 2200 − 2500 = −300 mmH2O.
DP Transmitter Level Measurement for Open Tanks

- Open tank
- H side connected at the zero level
- L side vented to atmosphere
- DP transmitter
- Liquid head h
DP Transmitter level measurements is used widely in various applications. Differential pressure transmitters are used for liquid level measurement, especially in open tanks.
When measuring level in a closed or pressurized tank, a DP measurement is necessary to compensate for vessel pressure.
In an open tank level measurement, the DP transmitter’s HP leg is connected to the bottom of the tank while the LP leg is open to the atmosphere.
Specific gravity, which is the density relative to the density of water, plays a crucial role in the configuration of the DP transmitter.
By determining the zero level and span level, the Lower Range Value (LRV) and Upper Range Value (URV) can be configured using a HART communicator.
Case 1 : DP Transmitter installed at the exact HP tapping point

Lets see DP Transmitter level measurements in case where DP Transmitter is installed at the exact HP (High Pressure) tapping point.
At Zero level = 0 mmwc
At Span level = H x Specific gravity
= 500 x 1.0
= 500 mmwc
Case 2 : DP Transmitter Installed Below Tapping Point for Open Tank


Lets see DP Transmitter level measurements in case where DP Transmitter is installed below tapping point for open tank.
If the transmitter is installed below the tank then it is called zero suppression.
The calculations will be as below:
When zero suppression is used then H1 height always filled with process fluid.
At zero level (LRV) = H1 x specific gravity
= 100 x 1.0
= 100 mmwc
At 100% level (URV) = (H1 + H2) x specific gravity
= (100 + 500) x 1.0
= 600 mmwc
Range = URV – LRV = 600 – 100 = 500 mmwc
To accurately configure the DP transmitter for level measurement in an open tank, we have to set the Lower Range Value (LRV) to 100 mmwc (millimeters of water column) and the Upper Range Value (URV) to 600 mmwc using a HART communicator
DP Transmitter Level Measurement for Closed Tanks
Lets see how DP Transmitter level measurements is used for closed tank applications.
Hydrostatic head instruments are utilized to measure liquid level in vessels operating above atmospheric pressure.
These instruments fully leverage the capabilities of differential pressure devices by connecting both sides of the measuring element to the vessel.
A differential pressure transmitter automatically subtracts the pressure on the LP (low pressure) side from the total pressure on the HP (high pressure) side. This configuration ensures that each increment of pressure above the liquid surface is counteracted by opposing capsule assemblies within the transmitter, resulting in cancellation.
Consequently, only the hydrostatic pressure exerted on the HP side contributes to the transmitter’s response, which is directly proportional to the level being measured.

The DP transmitter incorporates various pressure sensors such as diaphragms, capsules, and strain gauges to accurately measure the differential pressure. Depending on the specific pressure sensor used, the measured pressure is converted into parameters like millivolts, capacitance, or resistance.
To facilitate this conversion, a Wheatstone bridge is commonly employed, transforming the outputs of resistance, capacitance, or inductance-based pressure sensors into electrical signals such as millivolts or volts, proportionate to the pressure. Subsequently, the transmitter converts the pressure into an equivalent level signal.
In terms of installation, the tank’s bottom tapping point serves as the High Pressure (HP) tapping point, while the tank’s top tapping point functions as the Low Pressure (LP) tapping point.
The DP transmitter is connected to these HP and LP tapping points accordingly.
Please note that the calibration parameters of the DP transmitter may vary based on the specific installation and seal system employed.
Typically, three possible installation scenarios can be observed in the field.
| Installation Method | Advantages | Disadvantages |
|---|---|---|
| Transmitter installed Exactly at HP tapping point (Ideal & preferred way of installation) | Minimizes measurement errors and inaccuracies | Ensures accurate and reliable readings |
| Transmitter installed above HP tapping point | Reduces the chance of bubble formation in impulse line | May introduce errors due to potential bubble formation |
| Transmitter installed below HP tapping point | Effective compensation for measurement errors | May require additional calibration and adjustment |
The calibration process for the transmitter is determined by the specific installation method in the field. The calibration formula may vary slightly based on the installation type.
Two crucial parameters for every transmitter are the Lower Range Value (LRV) and Upper Range Value (URV). These values need to be calculated based on the installation method.
Wet Leg and Dry Leg Methods

Wet Leg: In this configuration, the LP impulse line is filled with liquid such as water, glycol, glycerin, or the same liquid present inside the tank.
Dry Leg: In this configuration, the LP impulse line is filled with air, gas, or any other gases.
The hydrostatic pressures applied to DP transmitters will vary depending on whether it is a wet leg or dry leg installation. It is important to consider these factors as the calibration formula will also vary accordingly.
The decision of whether a DP transmitter has a wet leg or dry leg configuration can be made based on its field installation and process application. In some cases, a dry leg installation can be converted to a wet leg by filling water into the LP impulse line.
Case 1 : Transmitter mounted leveled with the minimum level

With wet leg, Span = ρp • g • H , or, = SGp • h
With dry leg ; Span = ρp • g • H , or, = SGp • h
Case 2 : Transmitter mounted above the minimum level

With wet leg, Zero Elevation = − (ρf • g • x)
Span = ρp • g • H
With dry leg, It is not preferable
So, for calibration,
4mA (LRV) = Min. Head + Zero Elevation
20mA (URV) = Span + Zero Elevation
You may also read our article: Zero Elevation and Zero Suppression in Level Measurement
Case 3 : Transmitter mounted below the HP tap

With dry leg,
Pw at min. level = (SGf • x)
Pw at max. level = (SGf • x) + (SGp • H)
Span = SGp • H
With wet leg,
Zero Suppression = − (ρf • g • h) ,or, = − (SGf • h)
Span = ρp • g • H , or, = SGp • H
Therefore, for calibration;
4mA (0%) = Zero Elevation
20mA (100%) = Span+Zero Suppression
Case 4 : Transmitter mounted below HP tapping point and Minimum Level is Elevated

Wet Leg:
Minimum Wet Leg Pressure (Pw min): Calculated as (SGp • y) – (SGf • d)
Maximum Wet Leg Pressure (Pw max): Calculated as (SGp)(x + y) – (SGf • d)
Span: Calculated as ρp • g • x or SGp • x
Dry Leg:
Pressure at Minimum Level (Pw at min. level): Calculated as (SGf • z) + (SGp • y)
Pressure at Maximum Level (Pw at max. level): Calculated as (SGf • z) + (SGp)(x+y)
Span: Calculated as SGp • H
Please have a look with below variables and their definitions:
| Variable | Definition |
|---|---|
| ρp | Density of process liquid in the tank |
| ρf | Density of fill-liquid in the tubing |
| ρu | Density of upper liquid |
| ρl | Density of lower liquid |
| Pw | Equivalent head of water |
| SGp | Standard gravity of process liquid |
| SGf | Standard gravity of fill liquid |
| SGu | Standard gravity of upper liquid |
| SGl | Standard gravity of lower liquid |
DP Type Level Transmitter Range Formulas at a Glance
A dp type level transmitter calculates liquid level from the hydrostatic head between its HP and LP ports. The HP side is connected to the bottom tapping and the LP side is vented in an open tank or connected to the tank top in a closed tank. Level is found from ΔP = H × SG, where H is the liquid height above the HP tap in mm and SG is the specific gravity of the process liquid.

LRV and URV Formula Table
Symbols: H = measuring span (mm), SG = process liquid SG, h = height of HP tap above the transmitter (mm), Hw = wet leg height (mm), SGw = wet leg fill SG. Results are in mmH2O.
| Installation | LRV (0%) | URV (100%) |
|---|---|---|
| Open tank, transmitter at HP tap | 0 | H × SG |
| Open tank, transmitter h below HP tap | h × SG | (h + H) × SG |
| Closed tank, dry leg | 0 | H × SG |
| Closed tank, wet leg | minus Hw × SGw | H × SG minus Hw × SGw |
| Closed tank, wet leg, transmitter h below HP tap | h × SG minus Hw × SGw | (h + H) × SG minus Hw × SGw |
Quick Check Example
For H = 2000 mm, SG = 1.1 and a 2500 mm wet leg filled with water (SGw = 1.0), the range is LRV = minus 2500 mmH2O and URV = 2200 minus 2500 = minus 300 mmH2O. The calibrated span is still 2200 mmH2O, because the wet leg only shifts the range and does not change the span.
Keep the wet leg completely full and the dry leg free of condensate, otherwise the zero will drift.
Frequently Asked Questions (FAQs)
1. What is DP transmitter level measurement?
DP transmitter level measurement is a method of measuring liquid level by detecting the differential pressure created by the liquid column inside a tank. The pressure difference is converted into a level signal that can be monitored remotely.
2. Why is a DP transmitter used for level measurement?
A DP transmitter allows continuous level monitoring from a control room without physically checking the tank. It is especially useful in industrial applications where tanks are large, hazardous, pressurized, or located in remote areas.
3. How does a DP transmitter measure level in an open tank?
In an open tank, the high-pressure (HP) side of the transmitter is connected to the bottom of the tank, while the low-pressure (LP) side is exposed to atmospheric pressure. The measured differential pressure is directly proportional to the liquid level.
4. How does a DP transmitter measure level in a closed tank?
In a closed tank, the HP side is connected to the bottom of the tank and the LP side is connected to the vapor space at the top. The transmitter cancels out vessel pressure and measures only the hydrostatic pressure caused by the liquid level.
5. What is zero suppression in DP transmitter level measurement?
Zero suppression occurs when the DP transmitter is installed below the tank tapping point. The impulse line remains filled with liquid, creating additional pressure that shifts the transmitter’s lower range value (LRV) above zero.
6. What is zero elevation in DP transmitter calibration?
Zero elevation occurs when the transmitter is installed above the minimum liquid level. The transmitter experiences a negative pressure effect that requires the calibration range to be elevated accordingly.
7. What is the difference between wet leg and dry leg installations?
In a wet leg installation, the LP impulse line is filled with a liquid such as water or glycol. In a dry leg installation, the LP impulse line contains air or gas. The calibration formulas and pressure calculations differ for each configuration
I hope you like above blog. There is no cost associated in sharing the article in your social media. Thanks for Reading !! Happy Learning

3 Comments