Flow Measurement · Glossary

What is Pressure and Temperature Compensation?

gas and steam flow correctionFlow Measurement

Pressure and temperature compensation corrects gas or steam flow for density changes using live pressure and temperature measurements.

Advertisement

Pressure and Temperature Compensation Explained

A DP or volumetric gas meter is designed for one density. When line pressure or temperature changes, density changes and the uncompensated flow is wrong.

Compensation uses live absolute pressure and temperature, and Z where needed, to correct the flow in the DCS, a flow computer or a multivariable transmitter.

Pressure and Temperature Compensation Formula

Qcomp = Qdesign × √[(p ÷ pd) × (Td ÷ T) × (Zd ÷ Z)]
Qdesignflow from DP at design density (mass or standard volume)
p, Tactual absolute pressure and temperature
pd, Tddesign conditions
Example: Design 6 bar a, 20 °C; actual 5 bar a, 30 °C: factor √(5 ÷ 6 × 293.15 ÷ 303.15) = 0.898, so 1000 kg/h reads 898 kg/h.
Advertisement

Calculators for Pressure and Temperature Compensation

Frequently Asked Questions

What is Pressure and Temperature Compensation?

Pressure and temperature compensation corrects gas or steam flow for density changes using live pressure and temperature measurements.

Why is the DP compensation a square root?

DP meter flow is proportional to √(DP × density), so the density correction enters under the square root.

Is compensation needed for liquids?

Rarely for pressure. For large temperature changes the density correction can matter, especially for oils.