Temperature Measurement · Glossary

What is RTD Wiring (2, 3 and 4 Wire)?

lead resistance compensationTemperature Measurement

RTD wiring is the 2, 3 or 4 wire connection of an RTD; more wires cancel more of the lead wire resistance.

Advertisement

RTD Wiring (2, 3 and 4 Wire) Explained

In a 2 wire circuit the lead resistance adds to the RTD and reads as extra temperature. A 3 wire circuit cancels lead resistance if all leads are equal. A 4 wire circuit measures voltage on separate leads and removes lead effects fully.

Use 3 wire for most field RTDs and 4 wire for precision or long cable runs.

RTD Wiring (2, 3 and 4 Wire) Formula

Error (2 wire) ≈ Rloop ÷ 0.385 °C
Rlooptotal resistance of both leads (Ω)
0.385Pt100 slope in Ω per °C
Example: 2 × 5 m of 0.5 mm² copper ≈ 0.34 Ω, adding about 0.9 °C on a Pt100.
Advertisement

Calculators for RTD Wiring (2, 3 and 4 Wire)

Free Downloads

Free Tools

Frequently Asked Questions

What is RTD Wiring (2, 3 and 4 Wire)?

RTD wiring is the 2, 3 or 4 wire connection of an RTD; more wires cancel more of the lead wire resistance.

Can a 4 wire RTD be connected to a 3 wire input?

Yes, leave one lead unconnected. You lose the extra accuracy of 4 wire.

Why is head mount transmitter wiring short?

Mounting the transmitter in the head keeps RTD leads short and sends a robust 4 to 20 mA signal back.

You May Also Like

Learn more on the blog

Thermocouple and RTD installation precautions

A practical guide on instrumentationblog.in with more detail on RTD wiring (2, 3 and 4 Wire) and how it is applied on real plants.

Read Full Article

Related Terms

More Temperature Measurement Terms

All temperature measurement terms · Full glossary A to Z