Instrumentation Signal · Free Calculator

RTD Lead Wire Resistance Error Calculator

See how much error the cable adds to an RTD measurement with a 2 wire connection, and why 3 and 4 wire connections are used.

2 wire error3 wire4 wirePt100 and Pt1000
m
°C
The 2 wire error is large. Use a 3 or 4 wire connection, a Pt1000 or a head mounted transmitter.
Resistance of one conductor1.225 Ω
2 wire error+6.364 °C
3 wire error (matched leads)about 0 °C (only lead mismatch remains)
4 wire errorabout 0 °C
Sensor sensitivity0.385 Ω/°C
How this result was calculated
  1. R lead = length × Ω/km × (1 + 0.00393 (T − 20))
  2. Error = 2 × R lead ÷ (R0 × 0.00385) = 6.364 °C
Advertisement

Lead Resistance Error

2 wire error (°C) = 2 × Rlead ÷ (R0 × α), α = 0.00385 /°C
3 wire: lead resistances cancel if matched · 4 wire: no lead error

Conductor resistance from IEC 60228 class 2 at 20 °C (0.5 mm² 36.0, 0.75 mm² 24.5, 1.0 mm² 18.1, 1.5 mm² 12.1 Ω/km).

Worked example

50 m of 0.75 mm² cable adds 1.225 Ω per conductor at 20 °C. A 2 wire Pt100 then reads about 6.4 °C high; a Pt1000 only 0.64 °C.

Key insight: a 3 wire connection only cancels lead resistance if all three conductors match; a loose terminal on one lead brings the error straight back.
Advertisement

Frequently Asked Questions

How much error does a 2 wire RTD have?

About 2.6 °C per ohm of total lead resistance for a Pt100.

Why is 3 wire RTD common?

It cancels the lead resistance at low cost, good enough for most industrial measurements.

Is Pt1000 better for long cables?

Yes, its 10 times higher sensitivity makes lead errors 10 times smaller.