two valves from one outputControl Valve

Split range control uses one controller output to operate two valves, each over part of the signal range.

Advertisement

Split Range Control Explained

A typical split gives valve A the 0 to 50 % output and valve B 50 to 100 %. It is used for heating and cooling, or for a small and a large valve to widen rangeability.

Overlap or gaps at the split point cause bumps in control, so the ranges are set and tested carefully in the positioners or in the control system.

Split Range Control Formula

Valve opening = (Signal − Start) ÷ (End − Start) × 100 %
Start, Endsignal range assigned to that valve
Example: Valve B on 12 to 20 mA at 16 mA: (16 − 12) ÷ 8 = 50 % open.
Advertisement

Calculators for Split Range Control

Frequently Asked Questions

What is Split Range Control?

Split range control uses one controller output to operate two valves, each over part of the signal range.

Split in positioners or in the DCS?

Splitting in the DCS with two outputs is more flexible and easier to diagnose; positioner splitting saves an output.

Why does the loop gain change at the split?

The two valves have different capacities, so the process gain jumps.