Flow Measurement · Glossary

What is Turndown Ratio?

ratio, for example 10:1Flow Measurement

Turndown ratio is the maximum flow divided by the minimum flow a meter can measure within its stated accuracy.

Advertisement

Turndown Ratio Explained

Turndown, also called rangeability, shows how wide a flow range one meter can cover. A meter with 10:1 turndown and 100 m³/h maximum measures accurately down to 10 m³/h.

DP meters have limited turndown because DP falls with the square of flow. Magnetic, coriolis and ultrasonic meters usually offer much wider turndown.

Turndown Ratio Formula

Turndown = Qmax ÷ Qmin
Qmaxmaximum measurable flow
Qminminimum flow within the accuracy statement
Example: 100 m³/h maximum and 10 m³/h minimum give 10:1.

Turndown Ratio: Typical Values

Orifice with one DP transmitterabout 3:1 to 5:1
Vortexabout 10:1 to 20:1 for liquids
Magnetic and coriolisoften 100:1 or more
Advertisement

Calculators for Turndown Ratio

Frequently Asked Questions

What is Turndown Ratio?

Turndown ratio is the maximum flow divided by the minimum flow a meter can measure within its stated accuracy.

How can DP meter turndown be increased?

With stacked DP transmitters on different ranges, or a smart transmitter with good low range accuracy.

Is turndown the same as accuracy?

No. Turndown says over what range the stated accuracy applies; always check whether accuracy is % of rate or % of full scale.