HART Command List and Lookup

Look up any common HART command number to see what it does, whether it is universal or common practice, and whether it writes to the device.

Universal commandsCommon practiceRead or writeCommand lookup
This command changes the device. On a live loop, put the loop in manual and follow your change procedure first.
Command 35Write primary variable range values
ClassCommon practice
ActionWrite

All listed commands

NoCommandClassAction
0Read unique identifierUniversalRead
1Read primary variableUniversalRead
2Read loop current and percent of rangeUniversalRead
3Read dynamic variables and loop currentUniversalRead
6Write polling addressUniversalWrite
7Read loop configurationUniversalRead
8Read dynamic variable classificationsUniversalRead
9Read device variables with statusUniversalRead
11Read unique identifier associated with tagUniversalRead
12Read messageUniversalRead
13Read tag, descriptor, dateUniversalRead
14Read primary variable transducer informationUniversalRead
15Read device information (range, damping, transfer function)UniversalRead
16Read final assembly numberUniversalRead
17Write messageUniversalWrite
18Write tag, descriptor, dateUniversalWrite
19Write final assembly numberUniversalWrite
20Read long tagUniversalRead
21Read unique identifier associated with long tagUniversalRead
22Write long tagUniversalWrite
33Read device variablesCommon practiceRead
34Write primary variable damping valueCommon practiceWrite
35Write primary variable range valuesCommon practiceWrite
36Set primary variable upper range valueCommon practiceWrite
37Set primary variable lower range valueCommon practiceWrite
38Reset configuration changed flagUniversalWrite
40Enter or exit fixed current modeCommon practiceWrite
41Perform self testCommon practiceCommand
42Perform device resetCommon practiceCommand
43Set primary variable zeroCommon practiceWrite
44Write primary variable unitsCommon practiceWrite
45Trim loop current zeroCommon practiceWrite
46Trim loop current gainCommon practiceWrite
47Write primary variable transfer functionCommon practiceWrite
48Read additional device statusUniversalRead
59Write number of response preamblesCommon practiceWrite
Advertisement

HART Command Classes

Universal commands: supported by every HART device
Common practice commands: optional, widely implemented
Device specific commands: defined by each manufacturer (via the DD)

Worked example

Command 35 writes the LRV and URV of the primary variable; command 1 reads the primary variable value and units.

Key insight: a handheld that "sees" a device but cannot change a parameter often lacks the device description (DD) needed for device specific commands, not the universal ones.
Advertisement

Frequently Asked Questions

What is HART command 0?

Read unique identifier: it returns the manufacturer, device type and ID, and is used to find devices on the loop.

Which HART command changes the range?

Command 35 writes the range values; 36 and 37 set URV and LRV from the applied input.

What are device specific commands?

Commands defined by the manufacturer, accessed through the device description file.