Communication Protocols · Free Tool

RS485 Cable Length and Baud Rate Guide

Check whether an RS485 network will work: maximum cable length for your data rate, number of devices on the segment and the termination and biasing it needs.

Length vs speedUnit loadsTerminationBiasing
bit/s
m
Rule of thumb maximum length1,200 m
Planned length800 m (OK)
Total unit loads20 of 32
Maximum devices with this transceiver32

Typical length limits (twisted pair, 24 AWG class)

Data rateApprox. maximum length
9.6 to 93.75 kbit/s1200 m
187.5 kbit/s1000 m
500 kbit/s400 m
1.5 Mbit/s200 m
12 Mbit/s100 m
Advertisement

RS485 Design Rules

Rule of thumb: length (m) × data rate (bit/s) ≤ 10⁸, up to 1200 m
Up to 32 unit loads per segment without repeaters

The table shows the Profibus DP segment lengths, a widely used reference for RS485 networks. Use shielded twisted pair with 120 Ω characteristic impedance.

Worked example

At 19200 bit/s the rule allows the full 1200 m. At 500 kbit/s it drops to about 200 m by the rule (Profibus allows 400 m with type A cable).

Key insight: fit a 120 Ω terminator at both physical ends of the bus only, and bias resistors once per segment; most "random" RS485 errors are missing or extra terminators.
Advertisement

Frequently Asked Questions

What is the maximum RS485 cable length?

About 1200 m at low data rates; it decreases as speed increases.

How many devices can be on one RS485 segment?

32 unit loads; with 1/8 UL transceivers that is up to 256 devices.

Where do I put the termination resistors?

One 120 Ω resistor at each end of the trunk, never at stubs or in the middle.