Level Transmitter Fault Finder

Choose the level symptom for a radar, guided wave radar or DP level transmitter and get the likely causes with checks and fixes.

Radar levelDP levelLost echoWrong level
SymptomLevel reads wrong by a constant offset
Most likely causeWrong tank height or reference point (radar)
First checkCompare configured tank height with the drawing

Causes in order of likelihood

CauseHow to checkFix
Wrong tank height or reference point (radar)Compare configured tank height with the drawingCorrect the calibration distances
Wet leg level changed or evaporated (DP)Check the wet leg and refillRefill the wet leg and check LRV and URV
Density different from design (DP)Compare process density with the configured valueRe range for the actual density
Advertisement

Before You Start

  • Work under a permit, inform the control room and put the loop in manual or bypass the trip before touching a live instrument.
  • Compare with a manual dip, sight glass or other independent level.
  • For radar, look at the echo curve; for DP, check the impulse lines and wet leg.
  • Check that the tank geometry and range in the transmitter match the tank.

Level Transmitter Fault Finder: All Symptoms

Level reads wrong by a constant offset

Likely causeHow to checkFix
Wrong tank height or reference point (radar)Compare configured tank height with the drawingCorrect the calibration distances
Wet leg level changed or evaporated (DP)Check the wet leg and refillRefill the wet leg and check LRV and URV
Density different from design (DP)Compare process density with the configured valueRe range for the actual density

Level stuck, not changing

Likely causeHow to checkFix
Radar tracking a false echo (internals, nozzle)View the echo curveRecord a false echo map with the tank low
Blocked or isolated impulse line (DP)Check valves and linesOpen valves, clear lines
Build up on the antenna or probeInspect the antenna or probeClean; use air purge or a suitable antenna

Level jumps or is unstable

Likely causeHow to checkFix
Foam, turbulence or agitator (radar)Watch the echo amplitudeUse guided wave radar or a stilling well; increase damping
Fill stream hitting the radar beamCheck inlet positionRelocate the transmitter away from the fill stream
Pressure fluctuations on DP without compensationCompare with tank pressureUse a closed tank (wet or dry leg) configuration

Reads full when tank is not full

Likely causeHow to checkFix
Radar in the blocking (near) distanceCheck level against the blocking distanceRaise the nozzle or set maximum level below the blocking zone
Condensation or build up near the antennaInspect antennaClean, insulate the nozzle
Wet leg drained (DP closed tank)Check wet legRefill the wet leg

Lost echo alarm (radar)

Likely causeHow to checkFix
Low dielectric product or heavy foamCheck echo amplitude and thresholdLower threshold, use guided wave radar
Antenna coated or dirtyInspect antennaClean the antenna
Tank empty and bottom not visibleCheck actual levelEnable empty tank handling setting
Key insight: for radar, always look at the echo curve before changing settings; it shows immediately whether the transmitter sees the product, an internal or nothing at all.
Advertisement

Frequently Asked Questions

Why does my radar level transmitter show full?

Often the level is inside the blocking distance, or there is build up or condensation near the antenna.

What is a false echo map?

A stored map of unwanted reflections from tank internals that the transmitter ignores.

Why does DP level read wrong on a closed tank?

Common causes are an incorrect or drained wet leg, or a density different from the design value.