DP Flow Transmitter Fault Finder

Choose the flow measurement symptom and get the likely causes for DP flowmeters such as orifice plates and venturis, with checks and fixes.

Reads high or lowNo flow shownNegative flowUnstable
SymptomFlow reads too high
Most likely causeLP impulse line leaking or partly blocked
First checkIsolate and check the LP line; vent and look for free flow

Causes in order of likelihood

CauseHow to checkFix
LP impulse line leaking or partly blockedIsolate and check the LP line; vent and look for free flowRepair the leak, clear the LP line
Orifice installed backwards or wrong boreCheck plate tab marking and bore against the data sheetReinstall correctly or replace the plate
Actual density differs from design (gas or steam pressure or temperature changed)Compare actual pressure and temperature with the design valuesApply pressure and temperature compensation
Advertisement

Before You Start

  • Work under a permit, inform the control room and put the loop in manual or bypass the trip before touching a live instrument.
  • Check whether square root is applied in the transmitter or the DCS, not both.
  • Note the DP in mbar and the expected flow; use the square root relation to compare.
  • Check the manifold: both block valves open, equaliser closed.

DP Flow Transmitter Fault Finder: All Symptoms

Flow reads too high

Likely causeHow to checkFix
LP impulse line leaking or partly blockedIsolate and check the LP line; vent and look for free flowRepair the leak, clear the LP line
Orifice installed backwards or wrong boreCheck plate tab marking and bore against the data sheetReinstall correctly or replace the plate
Actual density differs from design (gas or steam pressure or temperature changed)Compare actual pressure and temperature with the design valuesApply pressure and temperature compensation

Flow reads too low

Likely causeHow to checkFix
Equaliser valve passing or openClose equaliser and see if reading risesClose or replace the manifold
HP impulse line partly blocked or leakingVent and check flow from HP lineClear or repair the HP line
Worn or damaged orifice edgeInspect the plate at the next opportunityReplace the plate

Shows zero flow while process is flowing

Likely causeHow to checkFix
Low flow cut off set too highCheck cut off value in transmitter or DCSSet cut off to a few % of flow
Both block valves closed or equaliser openCheck manifold valve positionsRestore correct valve positions
Transmitter in fixed current modeCheck HART statusReturn to normal mode

Negative flow or reading below zero

Likely causeHow to checkFix
HP and LP impulse lines swappedTrace lines from tapping to transmitterSwap the lines
Zero shift from trapped liquid or gasEqualise and read the zeroVent or drain lines, zero trim
Reverse flow in the processCheck pumps and valvesProcess issue, not instrument

Unstable or noisy flow reading

Likely causeHow to checkFix
Turbulence from upstream fittings (short straight run)Check straight lengths against ISO 5167 tablesAdd a flow conditioner or relocate the meter
Square root amplifying noise at low flowNoise worse near zeroSet a low flow cut off, add damping
Gas in liquid lines or liquid in gas linesCheck impulse line slopes and condensate potsCorrect slopes, fill pots, vent
Key insight: because flow follows the square root of DP, a small zero error in mbar becomes a large flow error at low flow. Always check the zero first.
Advertisement

Frequently Asked Questions

Why does my orifice flow read low?

Common causes are a passing equaliser valve, a blocked HP line or a worn orifice edge.

Can a DP flow transmitter show negative flow?

Yes, if HP and LP lines are swapped or the zero has shifted; reverse process flow is also possible.

What is a low flow cut off?

A setting that forces the flow to zero below a small percentage, because the square root amplifies noise near zero.