Control Valve Opening (% Travel) Calculator
Check a control valve selection: from the rated Cv, inherent characteristic and the required Cv at minimum, normal and maximum flow, find the valve opening at each point.
- Equal %: travel = 1 + ln(C/Cmax) ÷ ln R
- Openings: 35.4 %, 74.4 %, 88.3 %
Inherent Characteristic Equations
Equal percentage: C ÷ Cmax = R(x − 1) → x = 1 + ln(C/Cmax) ÷ ln R
Quick opening (approx.): C ÷ Cmax = √x
x is the travel as a fraction, C the required flow coefficient and R the inherent rangeability (often 30 to 50 for equal percentage globe valves). These are ideal inherent curves; real valves follow the manufacturer Cv table, which should be used for final checks.
Worked example
A Cv 150 equal percentage valve (R = 50) needing Cv 12, 55 and 95 opens about 35 %, 74 % and 88 %: a good selection, with the normal point in the upper middle of travel.
Frequently Asked Questions
What travel range is good for a control valve?
Many guidelines aim for roughly 10 to 20 % at minimum and 70 to 85 % at maximum flow, keeping control away from the seat and the fully open stop.
Why does an equal percentage valve open so far at low Cv?
Its Cv rises slowly at small openings, so a small Cv needs more travel than on a linear valve.
Should I use the inherent or installed characteristic?
Use the manufacturer Cv table for openings. The installed characteristic also depends on how the system pressure drop changes with flow.