Control Valve · Free Calculator

Control Valve Seat Leakage Class Calculator

Find the maximum seat leakage allowed for a control valve in each leakage class, for setting up a shop leak test.

Class II to VIIEC 60534-4ANSI/FCI 70-2Leak test
Kv
bar
inch
Allowable leakage0.1964 L/min
Allowable leakage0.01179 m³/h
Rated flow at test ΔP117.9 m³/h
How this result was calculated
  1. Rated flow = Kv × √ΔP = 63 × √3.5 = 117.9 m³/h
  2. Leakage = 0.01 % of rated flow = 0.1964 L/min
Advertisement

Leakage Class Limits

Class II: 0.5 % of rated capacity
Class III: 0.1 %   Class IV: 0.01 %
Class V: 5 × 10⁻⁴ mL/min per inch seat per psi ΔP (water)
Class VI: table by seat diameter (air)

Classes II to IV are tested with water at 3 to 4 bar ΔP (or maximum operating ΔP if lower) and expressed as a fraction of rated flow at that ΔP.

Worked example

A Kv 63 valve tested at 3.5 bar has a rated flow of 117.9 m³/h; Class IV allows 0.01 % of that, about 0.20 L/min.

Key insight: Class IV is standard for metal seated globe valves; Class V and VI need lapped or soft seats and enough actuator seat load, so check thrust too.
Advertisement

Frequently Asked Questions

What is Class IV leakage?

0.01 % of the valve’s rated capacity at the test pressure drop, typical for metal seated globe valves.

What does Class VI mean?

Bubble tight shutoff measured with air, usually requiring a soft seat. The allowance depends on seat diameter.

Is shop leakage the same as in service?

No. Wear, erosion and lower seat load can increase leakage in service; the class applies to the new valve under test conditions.