Instrumentation Signal · Free Calculator

Analog Signal Converter Calculator (Any Range to Any Range)

Convert a value from one analog range to another, such as 0 to 10 V to 4 to 20 mA, or 4 to 20 mA to an engineering range, as a signal isolator or converter does.

0 to 10 V4 to 20 mA1 to 5 VAny range
Output value14.4 mA
Percent of range65.00 %
How this result was calculated
  1. % = (x − in low) ÷ (in high − in low) = 65.00 %
  2. y = out low + % × (out high − out low) = 14.4 mA

Conversion table

%Input (V)Output (mA)
0 %04
25 %2.58
50 %512
75 %7.516
100 %1020
Advertisement

Linear Scaling

y = ylow + (x − xlow) ÷ (xhigh − xlow) × (yhigh − ylow)

Worked example

6.5 V on a 0 to 10 V input is 65 %, which a converter outputs as 4 + 0.65 × 16 = 14.4 mA.

Key insight: converting a 0 to 10 V signal to 4 to 20 mA near the source makes it immune to voltage drop and much less sensitive to noise on long cables.
Advertisement

Frequently Asked Questions

How do I convert 0 to 10 V to 4 to 20 mA?

mA = 4 + 1.6 × V. 5 V gives 12 mA.

How do I convert 4 to 20 mA to 1 to 5 V?

Pass the current through a 250 Ω resistor: 4 mA gives 1 V and 20 mA gives 5 V.

Is this the same as PLC scaling?

Yes, the same linear equation; the PLC analog scaling calculator also handles raw counts.