Fixed Gas Detector Bump Test and Calibration SOP
A procedure for testing and calibrating fixed gas detectors (catalytic, infrared, electrochemical) with certified test gas: bump test, zero and span calibration and a check of the alarms and control system signal.
Download
- Document control header (SOP ANA 002)
- Purpose, scope and references
- Safety, tools and prerequisites
- Numbered step by step procedure
- Acceptance criteria and records
- Approval block for sign off
1. Purpose
To make sure fixed gas detectors respond to gas, read correctly and raise their alarms, so leaks are detected in time.
2. Scope
Fixed point flammable gas detectors (catalytic and infrared) and toxic gas detectors (electrochemical) with 4 to 20 mA or digital outputs.
3. References
- Detector manufacturer manual and calibration adapter instructions
- Test gas certificates
- Fire and gas cause and effect matrix
- Site gas detection philosophy
4. Responsibilities
- Instrument technician: carries out the work and records results.
- Instrument engineer or supervisor: reviews and approves the records.
- Operations: grants the permit, isolates the process and returns the equipment to service.
5. Safety Precautions
- Work only under a valid permit to work and follow the site isolation (lockout tagout) procedure.
- Wear the PPE required for the area: safety helmet, glasses, gloves and safety shoes as a minimum.
- In hazardous areas use certified or intrinsically safe test equipment, or obtain a gas free certificate and hot work permit.
- Inform the control room before starting, and before returning the instrument to service.
- Inhibit only the detector under test and keep the inhibit time short; the area loses protection while inhibited.
- Handle test gas cylinders upright and secured; toxic test gas must be vented away from people.
6. Tools and Equipment
- Certified test gas of the correct gas and concentration (typically about 50 % LEL for flammable, near the alarm level for toxic) within expiry
- Zero gas (synthetic air or nitrogen as required) or clean air
- Calibration adapter (cup) and regulator with the flow rate given by the manufacturer
- Magnet or communicator to start calibration, and a radio
7. Prerequisites
- Permit approved; fire and gas system detector inhibited by operations.
- Test gas certificate checked; the detector sensor is not past its replacement date.
8. Procedure
8.1 Bump test (as found)
- Fit the calibration adapter and apply test gas at the manufacturer flow rate.
- Record the peak reading and the time to reach it; compare with the gas concentration.
- If the reading is within the acceptance band the detector passes the bump test; continue to calibration only if required by the schedule or if the bump test fails.
8.2 Zero calibration
- Apply zero gas or ensure clean air, start the zero routine and wait for it to finish.
- Record the zero reading.
8.3 Span calibration
- Enter the test gas concentration if required, apply test gas and start the span routine.
- Wait for the detector to accept the span, then remove the gas and record the as left span reading.
- Allow the reading to return to zero before ending the inhibit.
8.4 Alarm and output check
- With the control room, confirm the detector signal (mA or digital value) matches the local reading during gas application.
- Confirm the low and high alarms were seen at their set points where the test gas allows, or simulate the signal to check alarm actions.
- Remove the inhibit and confirm the detector is healthy in the system.
9. Acceptance Criteria
- Bump test reading within the site acceptance band (for example within ± 10 % of the applied concentration, or as set by the site procedure).
- As left span reading within the manufacturer tolerance.
- Zero stable at zero, and the control system reading matches the detector.
10. Records
Related tools
This is a generic procedure. Adapt it to your site permit system, the manufacturer instructions and your quality system before use.
Frequently Asked Questions
What is the difference between a bump test and a calibration?
A bump test only checks that the detector responds to gas; a calibration adjusts zero and span to read correctly.
Which test gas concentration should be used?
Usually about half of the measuring range for flammable detectors (around 50 % LEL) and close to the alarm level for toxic detectors, as the manufacturer recommends.
Can I calibrate an infrared methane detector with propane?
Only with the manufacturer cross calibration factor and procedure; using the target gas is preferred.