What is Analog Scaling?

raw counts to engineering unitsSignals and PLC

Analog scaling converts the raw value from a PLC analog input into engineering units such as bar or °C.

Advertisement

Analog Scaling Explained

The input card turns 4 to 20 mA into counts, for example 0 to 27648 on Siemens S7 cards. The program scales these linearly to the transmitter range.

Wrong raw limits or range values give errors at every point except where they happen to match.

Analog Scaling Formula

PV = LRV + (raw − rawmin) ÷ (rawmax − rawmin) × (URV − LRV)
rawcounts from the input card
LRV, URVengineering range
Example: S7 card 0 to 27648, range 0 to 10 bar, raw 13824: PV = 5.0 bar.
Advertisement

Calculators for Analog Scaling

Free Downloads

Frequently Asked Questions

What is Analog Scaling?

Analog scaling converts the raw value from a PLC analog input into engineering units such as bar or °C.

Why 27648 and not 32767?

Siemens leaves headroom above 100 % for overrange diagnostics.

Where should square root be applied?

In the transmitter or after scaling in the program, never both.