4 to 20 mA Cheat Sheet

Every formula and number you need for 4 to 20 mA loops on one printable page: scaling, square root, NAMUR fault levels, loop power and PLC raw counts.

One page A4Print ready PDFFree, no sign up

Download

4 to 20 mA Cheat Sheet PDF preview

A one page A4 sheet to print, pin up in the workshop or keep on your phone. Everything on it is also shown below.

Download PDF A4 · 89 KB

Scaling formulas

Signal from PVI = 4 + 16 × (PV − LRV) ÷ (URV − LRV)
PV from signalPV = LRV + (I − 4) ÷ 16 × (URV − LRV)
Percent of span% = (I − 4) ÷ 16 × 100
Signal from percentI = 4 + 0.16 × %
Across 250 Ω4 to 20 mA gives 1 to 5 V

Percent to mA

%mAV (250 Ω)
04.001.00
105.601.40
258.002.00
5012.003.00
7516.004.00
9018.404.60
10020.005.00

Square root (DP flow)

Flow from DPQ% = 10 × √(DP%)
SignalI = 4 + 16 × √(DP ÷ DPmax)
DP from flowDP% = (Q%)² ÷ 100
Example25 % DP = 50 % flow = 12 mA

Apply square root once only: in the transmitter or in the DCS, never both. Use a low flow cut off (typically 5 to 10 % flow).

Advertisement

NAMUR NE 43 signal levels

RangeMeaning
3.8 to 20.5 mAValid measurement (saturation limits)
≤ 3.6 mAFailure, downscale
≥ 21.0 mAFailure, upscale
3.6 to 3.8 or 20.5 to 21.0 mAUndefined; treat as suspect

Loop power

Supply neededVs ≥ Vtx,min + Imax × (Rload + Rcable + Rbarrier)
Maximum loop resistanceRmax = (Vs − Vtx,min) ÷ Imax
Use Imaxabout 22 to 23 mA (alarm current, from the data sheet)

HART essentials

  • Digital signal: FSK, 1200 Hz = 1, 2200 Hz = 0, about 1 mA peak to peak on top of the analog signal
  • Loop needs at least 230 Ω (250 Ω typical) for HART communication
  • Multidrop: transmitters fixed at 4 mA, polling addresses 1 to 63
  • Up to 4 variables: PV, SV, TV, QV

PLC raw count scaling

GeneralPV = LRV + (raw − rawmin) ÷ (rawmax − rawmin) × span
Siemens S7 (4 to 20 mA)0 to 27648 = 0 to 100 %
16 bit unsigned0 to 65535

Quick fault finding

ReadingLikely cause
0 mAOpen loop, no supply, blown fuse
3.6 mA or lessTransmitter fault (downscale alarm)
Stuck at 4 mAWrong range, isolated or blocked impulse line
Over 20.5 mAOver range or upscale alarm
Noisy readingShield earthed at both ends, AC nearby, poor terminal

2 wire, 3 wire, 4 wire

  • 2 wire: loop powered, signal and power share two wires
  • 3 wire: common negative for supply and signal
  • 4 wire: separate mains or 24 V supply, active output
  • Live zero (4 mA) detects broken wires; 0 to 20 mA cannot

Related Calculators and Tools

Advertisement

Frequently Asked Questions

What is 50 % in 4 to 20 mA?

12 mA. The signal is 4 mA plus 16 mA times the fraction of span.

What does 3.6 mA mean on a transmitter?

Under NAMUR NE 43 a current of 3.6 mA or less signals a transmitter failure (downscale alarm).

Why does a 4 to 20 mA loop start at 4 mA?

The live zero powers 2 wire transmitters and lets the receiver tell a real zero from a broken wire (0 mA).