Signals and PLC · Glossary

What is Live Zero?

4 mA at 0 %Signals and PLC

Live zero means the lowest signal value (4 mA) is above zero, so a broken loop (0 mA) can be told apart from a real zero reading.

Advertisement

Live Zero Explained

With 0 to 20 mA a broken wire looks like a valid zero. With 4 to 20 mA anything well below 4 mA is a fault.

The 4 mA also supplies the operating current that two wire transmitters need.

Live Zero: Typical Values

Normal range4 to 20 mA
Common broken loop indicationbelow about 3.6 mA (NAMUR NE43)
Advertisement

Calculators for Live Zero

Free Downloads

Frequently Asked Questions

What is Live Zero?

Live zero means the lowest signal value (4 mA) is above zero, so a broken loop (0 mA) can be told apart from a real zero reading.

Is 1 to 5 V also live zero?

Yes, 1 to 5 V is the voltage form, often from 4 to 20 mA across 250 Ω.

Can a transmitter go below 4 mA?

Slightly, to show under range, and to about 3.6 mA or less for a fault.