Pressure Measurement · Glossary

What is Zero Elevation and Suppression?

range offset from liquid legsPressure Measurement

Zero elevation and suppression shift a transmitter range to cancel the head of liquid in impulse lines or seal capillaries.

Advertisement

Zero Elevation and Suppression Explained

If a transmitter is mounted below its tap with a filled line, it sees extra pressure at zero level, so the range starts above zero: a suppressed zero range such as 20 to 120 kPa.

If a wet leg or seal capillary on the low side adds pressure there, the range starts below zero: an elevated zero range such as −80 to 20 kPa. These terms follow ISA 51.1.

Zero Elevation and Suppression Formula

Offset = ρleg × g × hleg
ρlegdensity of liquid in the leg or capillary
hlegvertical height of the leg
Example: A transmitter 2 m below its tap on a water filled line sees 1000 × 9.80665 × 2 ≈ 19.6 kPa at zero level.
Advertisement

Calculators for Zero Elevation and Suppression

Frequently Asked Questions

What is Zero Elevation and Suppression?

Zero elevation and suppression shift a transmitter range to cancel the head of liquid in impulse lines or seal capillaries.

How do I remember which is which?

Suppressed zero: zero of the measured variable is below the LRV (LRV positive). Elevated zero: zero is above the LRV (LRV negative).

Can I just zero the transmitter instead?

You can set the LRV with the legs filled at zero level, but you must still keep the span the same.