What is Zero Elevation and Suppression?
Zero elevation and suppression shift a transmitter range to cancel the head of liquid in impulse lines or seal capillaries.
Zero Elevation and Suppression Explained
If a transmitter is mounted below its tap with a filled line, it sees extra pressure at zero level, so the range starts above zero: a suppressed zero range such as 20 to 120 kPa.
If a wet leg or seal capillary on the low side adds pressure there, the range starts below zero: an elevated zero range such as −80 to 20 kPa. These terms follow ISA 51.1.
Zero Elevation and Suppression Formula
| ρleg | density of liquid in the leg or capillary |
| hleg | vertical height of the leg |
Calculators for Zero Elevation and Suppression
Frequently Asked Questions
What is Zero Elevation and Suppression?
Zero elevation and suppression shift a transmitter range to cancel the head of liquid in impulse lines or seal capillaries.
How do I remember which is which?
Suppressed zero: zero of the measured variable is below the LRV (LRV positive). Elevated zero: zero is above the LRV (LRV negative).
Can I just zero the transmitter instead?
You can set the LRV with the legs filled at zero level, but you must still keep the span the same.