Free engineering calculators and unit convertersceo@instrumentationblog.in
IP, NEMA and Ex Rating Decoder · Free Tool

NEMA Enclosure Types and IP Equivalents

Choose a NEMA enclosure type to see what it protects against and the IP rating it is generally considered to meet, with the full NEMA 250 type list.

NEMA 250NEMA 4XIP cross referenceIndoor and outdoor
NEMA 4XAs Type 4, plus corrosion resistance
LocationIndoor or outdoor
Meets at leastIP66

NEMA enclosure types

TypeLocationProtectionIP (minimum)
NEMA 1IndoorProtection against contact and falling dirtIP10
NEMA 2IndoorAdds protection against dripping and light splashing waterIP11
NEMA 3Indoor or outdoorRain, sleet, snow, windblown dust; undamaged by external iceIP54
NEMA 3RIndoor or outdoorRain, sleet, snow; undamaged by external ice (no dust protection)IP14
NEMA 3SIndoor or outdoorAs Type 3, and external mechanisms stay operable when ice ladenIP54
NEMA 4Indoor or outdoorWindblown dust and rain, splashing and hose directed waterIP66
NEMA 4XIndoor or outdoorAs Type 4, plus corrosion resistanceIP66
NEMA 5IndoorSettling airborne dust, lint, fibres; dripping and light splashing waterIP52
NEMA 6Indoor or outdoorHose directed water and temporary submersion at limited depthIP67
NEMA 6PIndoor or outdoorAs Type 6, plus prolonged submersion at limited depthIP68
NEMA 7IndoorHazardous locations, Class I Division 1 gases (explosion proof)n/a
NEMA 8Indoor or outdoorHazardous locations, Class I, oil immersed equipmentn/a
NEMA 9IndoorHazardous locations, Class II combustible dustsn/a
NEMA 10MiningMeets MSHA requirements for minesn/a
NEMA 12IndoorCirculating dust, lint, fibres; dripping and light splashing non corrosive liquidsIP52
NEMA 12KIndoorAs Type 12, with knockoutsIP52
NEMA 13IndoorDust, lint; spraying, splashing and seepage of oil and non corrosive coolantsIP54
Advertisement

NEMA and IP Are Not Interchangeable

NEMA 250 enclosure types include tests that IEC 60529 does not, such as corrosion, icing, oil and gasket ageing. A NEMA type can therefore be said to meet or exceed the listed IP code, but an IP rated enclosure cannot automatically be called a NEMA type.

NEMA 4X ⇒ meets IP66    IP66 ⇏ NEMA 4X (corrosion and other tests not covered)

Worked example

A stainless steel transmitter housing on a food plant washdown line needs hose down and corrosion resistance: NEMA 4X, which also satisfies an IP66 requirement.

Key insight: NEMA 7 and 9 are hazardous location ratings, not ingress ratings. For gas and dust zones also check the Ex marking or Class/Division certification.
Advertisement

Frequently Asked Questions

What is a NEMA 4X enclosure?

An indoor or outdoor enclosure protected against windblown dust, rain, splashing and hose directed water, and also corrosion resistant, usually stainless steel or plastic.

What is the IP equivalent of NEMA 4X?

It is generally accepted to meet IP66, but the reverse is not true because NEMA adds corrosion and other tests.

What is the difference between NEMA 12 and NEMA 4?

NEMA 12 is for indoor use against dust and dripping liquids; NEMA 4 adds hose directed water and outdoor use.

You May Also Like

Learn more on the blog

Hazardous area classification zones

A practical, field focused guide on instrumentationblog.in that explains the theory behind this tool and how engineers apply it on real plants.

Read Full Article

More IP, NEMA and Ex Rating Decoder