PID Units Converter: Gain, PB, Repeats and Ki

Convert PID settings between the units used by different controllers: gain or proportional band, integral time or repeats per minute, and ideal or parallel gains.

Gain ↔ PBTi ↔ repeats/minIdeal ↔ parallelMinutes ↔ seconds
min
min
Proportional band50 %
Repeats per minute0.25
Parallel Ki0.5 per min

All conversions

QuantityValue
Proportional band50 %
Integral time4 min = 240 s
Integral as repeats per minute0.25
Integral as repeats per second0.004167
Parallel Ki = Kc ÷ Ti0.5 per min = 0.008333 per s
Parallel Kd = Kc × Td1 min = 60 s
Derivative time0.5 min = 30 s
Advertisement

Conversions

PB (%) = 100 ÷ Kc
Repeats per minute = 1 ÷ Ti (min)
Ki = Kc ÷ Ti, Kd = Kc × Td (ideal to parallel)

Ideal (ISA) form: u = Kc [e + (1/Ti) ∫e dt + Td de/dt]. Parallel form: u = Kp e + Ki ∫e dt + Kd de/dt.

Worked example

Kc = 2, Ti = 4 min, Td = 0.5 min: PB = 50 %, 0.25 repeats per minute, Ki = 0.5 per min, Kd = 1 min.

Key insight: mixing up repeats per minute and minutes per repeat is a classic tuning error: entering 4 instead of 0.25 makes the integral sixteen times stronger.
Advertisement

Frequently Asked Questions

Is integral time the same as reset rate?

No. Reset rate (repeats per minute) is the inverse of integral time (minutes per repeat).

What is proportional band?

100 ÷ gain, in %: the error that drives the output through its full range.

Which form does my controller use?

Check the manual; DCS often use ideal or series, PLCs often parallel.