PID Tuning Tools · Free Tool

Step Test FOPDT Model Calculator

Turn an open loop step test into a first order plus dead time model. Enter the output step, the PV change and the times when the PV reached 28 % and 63 % of its change.

Process gain KDead time θTime constant τTwo point method
%
%
%
min
min
Process gain K1.5 %/%
Time constant τ2.25 min
Dead time θ1.75 min
θ/τ ratio0.778
Suggested lambda PI (λ = max(τ, 3θ))Kc = 0.214, Ti = 2.25 min
How this result was calculated
  1. K = ΔPV ÷ ΔOP = 15 ÷ 10
  2. τ = 1.5 × (t63 − t28)
  3. θ = t63 − τ
Advertisement

Two Point Method (Smith)

K = ΔPV ÷ ΔOP
τ = 1.5 (t₆₃ − t₂₈)
θ = t₆₃ − τ

t₂₈ and t₆₃ are the times, measured from the output step, when the PV has completed 28.3 % and 63.2 % of its total change. ΔPV and ΔOP in % of range.

Worked example

OP step 10 %, PV 40 → 55 %, t₂₈ = 2.5 min, t₆₃ = 4 min: K = 1.5, τ = 2.25 min, θ = 1.75 min.

Key insight: make the step in manual, with the process steady, large enough to see clearly above noise (often 5 to 10 %), and wait for the PV to settle before reading the final value.
Advertisement

Frequently Asked Questions

What is a FOPDT model?

First order plus dead time: a process described by gain, time constant and dead time, used by most tuning rules.

Why use 28 % and 63 %?

For a first order response these points give τ and θ with simple formulas (Smith method).

What if the PV keeps ramping?

The process is integrating (like level); use integrating tuning rules instead.