PLC Digital Signal · Free Calculator

PLC Scan and Response Time Calculator

Estimate how long a PLC takes to react: from a field input changing to the output switching. The result combines input filter delay, scan time and output module delay for typical and worst cases.

Scan timeInput filterWorst caseOutput delay
ms
ms
ms
ms
ms
Worst case PLC response44 ms
Typical PLC response24 ms
Worst case including field device59 ms
Minimum pulse reliably seen23 ms
Your pulsedetected every time
How this result was calculated
  1. Typical = input filter + 1 scan + output delay = 24 ms
  2. Worst = input filter + 2 scans + output delay = 44 ms
  3. Minimum pulse width = input filter + 1 scan = 23 ms
Advertisement

Response Time Formulas

Typical response = tfilter + tscan + tout
Worst case = tfilter + 2 × tscan + tout
Minimum detectable pulse = tfilter + tscan

The worst case occurs when the input changes just after the PLC has read its inputs: the change waits almost one full scan to be read, then a second scan to be executed and written to the outputs. Module delays come from the I/O datasheet; network I/O adds its update time.

Worked example

With a 20 ms scan, 3 ms input filter and 1 ms output delay, the PLC typically reacts in 24 ms and in the worst case in 44 ms. A 15 ms relay brings the total to 59 ms.

Key insight: for safety functions and fast machines, use the worst case, not the typical value. Remote I/O on a network adds its own update time on both input and output.
Advertisement

Frequently Asked Questions

Why can the response take two scans?

Inputs are read at the start of the scan and outputs written at the end. A change just after the input read waits for the next scan.

How do I catch very short pulses?

Use a high speed counter, an interrupt (event) input or a module with pulse catch, or lengthen the pulse in the field device.

What is the input filter?

A debounce delay in the input module that rejects noise and contact bounce. Many modules let you set it from about 0.1 ms to 20 ms.