Pressure Measurement · Glossary

What is Transmitter Turndown?

URL ÷ calibrated spanPressure Measurement

Transmitter turndown is how far a transmitter span is reduced from its sensor upper range limit.

Advertisement

Transmitter Turndown Explained

Smart transmitters can be ranged far below their URL, often 100:1 on paper. The catch is accuracy: errors stated in % of URL become large percentages of a small span.

Choose a sensor range so the calibrated span uses a reasonable part of the URL, and check the maker accuracy formula at the turndown you need.

Transmitter Turndown Formula

Turndown = URL ÷ (URV − LRV)
URLupper range limit
URV − LRVcalibrated span
Example: A 0 to 2 bar span on a 20 bar URL sensor is 10:1.
Advertisement

Calculators for Transmitter Turndown

Frequently Asked Questions

What is Transmitter Turndown?

Transmitter turndown is how far a transmitter span is reduced from its sensor upper range limit.

Is high turndown always bad?

No, but accuracy and stability worsen as span shrinks. Check the total probable error at the needed span.

Is transmitter turndown the same as flow meter turndown?

No. Flow meter turndown is the ratio of maximum to minimum measurable flow; transmitter turndown is the ratio of sensor limit to span.