Free engineering calculators and unit convertersceo@instrumentationblog.in
Pressure Measurement · Free Calculator

Pressure Transmitter Turndown Calculator

Check whether a transmitter can be calibrated to your required span. Turndown compares the sensor upper range limit (URL) with the calibrated span.

URLCalibrated spanRangedownAccuracy impact
mbar
mbar
mbar
: 1
% of span
The calibration is within the transmitter limits. Check the datasheet: many accuracy specs only hold up to about 10 : 1 turndown and degrade beyond it.
Turndown10 : 1
Minimum span allowed25 mbar
Accuracy in units± 0.1625 mbar
How this result was calculated
  1. Turndown = URL ÷ span = 2,500 ÷ 250 = 10 : 1
Advertisement

Turndown Formula

Turndown = URL ÷ (URV − LRV)
Minimum span = URL ÷ maximum turndown

Worked example

A 2500 mbar sensor calibrated 0 to 250 mbar has a 10 : 1 turndown, comfortably within a 100 : 1 maximum.

Key insight: high turndown keeps spares simple but costs accuracy and stability. For best performance select a sensor range so the turndown stays below about 10 : 1.
Advertisement

Frequently Asked Questions

What is transmitter turndown?

The ratio of the sensor upper range limit to the calibrated span; also called rangedown or rangeability.

Does high turndown reduce accuracy?

Usually yes. Beyond a vendor stated limit (often 10 : 1) the accuracy specification is multiplied by a turndown factor.

What is URL?

Upper range limit: the highest pressure the sensor can be calibrated to measure.

You May Also Like

Learn more on the blog

Pressure transmitter installation tips

A practical, field focused guide on instrumentationblog.in that explains the theory behind this calculator and how engineers apply it on real plants.

Read Full Article

More Pressure Measurement Calculators

More Calculator Categories