Free engineering calculators and unit convertersceo@instrumentationblog.in
Electrical · Free Calculator

Cable Short Circuit Rating Calculator

Check that a cable or protective earth conductor can survive a fault until the protection operates, using the adiabatic equation from IEC 60364.

Adiabatic equationEarth conductor sizek factorFault withstand
kA
s
Minimum size55 mm²
Next standard size70 mm²
Let through energy I²t40,000,000 A²s
How this result was calculated
  1. S = I × √t ÷ k = 10,000 × √0.4 ÷ 115 = 55 mm²
Advertisement

The Adiabatic Equation

S = √(I² × t) ÷ k
Imax = k × S ÷ √t

S is conductor size (mm²), I the fault current (A), t the disconnection time (s) and k a factor for conductor material and insulation (IEC 60364-5-54). Valid for t up to 5 s.

Worked example

A 10 kA fault cleared in 0.4 s on PVC insulated copper: S = 10,000 × √0.4 ÷ 115 = 55 mm², so use 70 mm².

Key insight: for fast acting fuses and breakers, use the let through energy (I²t) from the manufacturer instead of I² × t, which often allows a much smaller earth conductor.
Advertisement

Frequently Asked Questions

What is the k factor for copper PVC cable?

k = 115 for copper conductors with PVC insulation up to 300 mm², and 143 for XLPE or EPR.

When is the adiabatic equation valid?

For disconnection times up to 5 seconds, when the heat has no time to escape from the conductor.

Can I use this for protective earth conductors?

Yes. It is the standard method in IEC 60364 and BS 7671 to check that a CPC survives an earth fault.

You May Also Like

Learn more on the blog

Cable sizing and ampacity explained

A practical, field focused guide on instrumentationblog.in that explains the theory behind this calculator and how engineers apply it on real plants.

Read Full Article

More Electrical Calculators

More Calculator Categories