Free engineering calculators and unit convertersceo@instrumentationblog.in
Electrical · Free Calculator

Cable Size and Voltage Drop Calculator

Calculate the voltage drop along a cable and find the smallest standard size that keeps it within your limit. Conductor resistance is corrected to operating temperature.

DC, 1 phase, 3 phaseCopper and aluminiumMinimum cable sizemm² sizes
V
A
m
cos φ
°C
%
Within the voltage drop limit. Check current carrying capacity and short circuit rating separately.
Voltage drop9.856 V
Voltage drop2.37 %
Voltage at load405.14 V
Minimum size for 3 %16 mm²
Conductor resistance1.289 Ω/km
How this result was calculated
  1. ρ at 70 °C = 0.017241 × (1 + 0.00393 × (70 − 20)) = 0.020629 Ω·mm²/m
  2. Vd = √3 × I × L × (R cos φ + X sin φ), X = 0.08 Ω/km assumed
  3. Vd = 9.856 V = 2.37 % of 415 V

Voltage drop for each standard size

SizeResistanceVoltage dropPercent
1.5 mm²13.75 Ω/km101.6 V24.48 %
2.5 mm²8.252 Ω/km61.11 V14.72 %
4 mm²5.157 Ω/km38.33 V9.24 %
6 mm²3.438 Ω/km25.67 V6.19 %
10 mm²2.063 Ω/km15.55 V3.75 %
16 mm²1.289 Ω/km9.856 V2.37 %
25 mm²0.8252 Ω/km6.439 V1.55 %
35 mm²0.5894 Ω/km4.704 V1.13 %
50 mm²0.4126 Ω/km3.402 V0.82 %
70 mm²0.2947 Ω/km2.534 V0.61 %
95 mm²0.2171 Ω/km1.963 V0.47 %
120 mm²0.1719 Ω/km1.63 V0.39 %
150 mm²0.1375 Ω/km1.377 V0.33 %
185 mm²0.1115 Ω/km1.186 V0.29 %
240 mm²0.08595 Ω/km0.9977 V0.24 %
300 mm²0.06876 Ω/km0.8711 V0.21 %
Advertisement

Voltage Drop Formulas

DC: Vd = 2 × I × L × R
Single phase: Vd = 2 × I × L × (R cos φ + X sin φ)
Three phase: Vd = √3 × I × L × (R cos φ + X sin φ)

R is the conductor resistance per metre at operating temperature, from ρ = ρ20 × (1 + α(T − 20)) ÷ A, with ρ20 = 0.017241 Ω·mm²/m for copper and 0.028264 for aluminium. Reactance X is taken as 0.08 Ω/km, typical of multicore LV cable.

Worked example

A 415 V three phase load draws 50 A over 100 m of 16 mm² copper at 70 °C, pf 0.85. R = 1.289 Ω/km and the drop is about 9.9 V, or 2.4 %, within a 3 % limit.

Key insight: voltage drop is only one of three cable sizing checks. The cable must also carry the current for its installation method and withstand the fault current until the protection trips.
Advertisement

Frequently Asked Questions

What is the maximum allowed voltage drop?

Many standards and specifications allow 3 % for lighting and 5 % for other loads from the supply point. Check your local wiring rules and project specification.

Why is cable resistance corrected for temperature?

Copper resistance rises about 0.4 % per °C. A cable at 70 °C has about 20 % more resistance than at 20 °C, so using 20 °C values underestimates voltage drop.

Does this calculator check cable ampacity?

No. It checks voltage drop only. Current carrying capacity depends on insulation, installation method, grouping and ambient temperature and must be checked against the cable standard.

You May Also Like

Learn more on the blog

Cable sizing and ampacity explained

A practical, field focused guide on instrumentationblog.in that explains the theory behind this calculator and how engineers apply it on real plants.

Read Full Article

More Electrical Calculators

More Calculator Categories