PLC, 4 to 20 mA and Modbus Quiz
Test yourself with 15 multiple choice questions. Check your answers to get a score and an explanation for every question.
PLC, 4 to 20 mA and Modbus Quiz: 15 Questions
Choose one answer for each question, then press Check answers. Explanations appear after checking.
1. 4 mA in a 4 to 20 mA loop represents:
2. 50 % of span equals:
3. Under NAMUR NE 43, a downscale failure signal is:
4. 4 to 20 mA through a 250 Ω resistor gives:
5. HART communication needs a loop resistance of at least about:
6. Siemens S7 analog input full range (4 to 20 mA) corresponds to:
7. A 12 bit ADC has how many counts?
8. A PLC scan cycle is:
9. Holding register 40001 is read with Modbus function code:
10. A TON timer:
11. A 2 wire transmitter is:
12. Instrument cable screens should normally be earthed:
13. A sinking digital input (PNP sensor) means the sensor:
14. Modbus RTU uses which error check?
15. IEEE 754 single precision float uses:
About this Quiz
15 multiple choice questions on plc, 4 to 20 ma and modbus, the kind asked in instrumentation interviews, technician exams and plant training. Each answer comes with a short explanation, so the quiz works as a revision sheet too.
Show answer key
- 0 % of range (live zero): Live zero lets broken wires (0 mA) be detected.
- 12 mA: 4 + 16 × 0.5 = 12 mA.
- ≤ 3.6 mA: Failure: ≤ 3.6 mA or ≥ 21 mA.
- 1 to 5 V: 0.004 × 250 = 1 V, 0.02 × 250 = 5 V.
- 230 Ω: At least 230 Ω, typically 250 Ω.
- 0 to 27648: Siemens nominal range is 0 to 27648.
- 4096: 2¹² = 4096.
- Read inputs, execute program, write outputs: Input scan, logic execution, output update, housekeeping.
- 03: FC 03 reads holding registers; FC 04 reads input registers.
- Delays turning on: TON is an on delay timer.
- Loop powered by the 4 to 20 mA signal: Power and signal share the two wires.
- At one end (control room): Single point earthing avoids earth loops.
- Sources current into the input: A PNP sensor sources current into a sinking input.
- CRC 16: RTU uses a CRC 16; ASCII uses LRC.
- 32 bits (two Modbus registers): A 32 bit float occupies two 16 bit registers.
Frequently Asked Questions
Is this quiz free?
Yes. No sign up is needed and you can retake it as often as you like.
Are the answers explained?
Yes. After you check your answers, each question shows the correct answer and a short explanation.
Where can I find more questions?
See the Interview Q&A section of instrumentationblog.in and the linked article below.
Learn more on the blog
75 industrial communication protocols MCQs
A practical, field focused guide on instrumentationblog.in that explains the theory behind this tool and how engineers apply it on real plants.
Read Full Article