SIS and Hazardous Area Quiz
Test yourself with 15 multiple choice questions. Check your answers to get a score and an explanation for every question.
SIS and Hazardous Area Quiz: 15 Questions
Choose one answer for each question, then press Check answers. Explanations appear after checking.
1. SIL stands for:
2. IEC 61511 applies to:
3. PFDavg for SIL 2 (low demand) is:
4. 2oo3 voting means:
5. Proof testing aims to reveal:
6. Zone 1 is an area where an explosive gas atmosphere is:
7. Equipment marked Ex ia can be used in:
8. Gas group IIC includes:
9. T4 temperature class means maximum surface temperature of:
10. Ex d protection concept is:
11. EPL Gb corresponds to:
12. A de energise to trip SIS output means:
13. Safe failure fraction (SFF) considers:
14. A bypass of a SIF during maintenance requires:
15. LOPA is used to:
About this Quiz
15 multiple choice questions on sis and hazardous area, the kind asked in instrumentation interviews, technician exams and plant training. Each answer comes with a short explanation, so the quiz works as a revision sheet too.
Show answer key
- Safety Integrity Level: Defined in IEC 61508 and IEC 61511.
- Safety instrumented systems in the process industry: It is the process sector standard for SIS.
- ≥ 10⁻³ to < 10⁻²: SIL 1: 10⁻² to 10⁻¹, SIL 2: 10⁻³ to 10⁻², SIL 3: 10⁻⁴ to 10⁻³.
- Two of three sensors must trip: It balances safety and spurious trips.
- Dangerous undetected failures: Proof tests find failures the system cannot detect itself.
- Likely in normal operation: Zone 0 continuous, zone 1 likely, zone 2 unlikely.
- Zones 0, 1 and 2: ia is the highest intrinsic safety level.
- Hydrogen and acetylene: IIC is the most easily ignited group.
- 135 °C: T1 450, T2 300, T3 200, T4 135, T5 100, T6 85 °C.
- Flameproof enclosure: Ex d contains an internal explosion.
- Zone 1: Ga zone 0, Gb zone 1, Gc zone 2.
- Loss of power causes the safe action: Fail safe design: power loss leads to the safe state.
- Safe and dangerous detected failures as a share of all failures: SFF = (λS + λDD) ÷ total λ.
- Authorisation and compensating measures: Bypasses must be controlled under the site procedure.
- Determine the required risk reduction and SIL target: Layer of protection analysis sets the SIL target.
Frequently Asked Questions
Is this quiz free?
Yes. No sign up is needed and you can retake it as often as you like.
Are the answers explained?
Yes. After you check your answers, each question shows the correct answer and a short explanation.
Where can I find more questions?
See the Interview Q&A section of instrumentationblog.in and the linked article below.
Learn more on the blog
Hazardous area classification: zones
A practical, field focused guide on instrumentationblog.in that explains the theory behind this tool and how engineers apply it on real plants.
Read Full Article