Temperature Measurement Quiz
Test yourself with 15 multiple choice questions. Check your answers to get a score and an explanation for every question.
Temperature Measurement Quiz: 15 Questions
Choose one answer for each question, then press Check answers. Explanations appear after checking.
1. A Pt100 has a resistance of:
2. The resistance of a Pt100 at 100 °C is about:
3. Which thermocouple type has the widest common use and range up to about 1200 °C?
4. The 3 wire RTD connection is used to:
5. Cold junction compensation is needed for:
6. In ANSI MC96.1 thermocouple colours, the negative wire is:
7. Under IEC 60584-3, type K positive conductor colour is:
8. A shorted thermocouple extension cable makes the reading:
9. RTDs are generally preferred over thermocouples for:
10. A thermowell is used to:
11. Class A tolerance of a Pt100 at 100 °C is:
12. °F for 100 °C is:
13. Thermowell wake frequency calculation is covered by:
14. Burnout direction in a temperature transmitter decides:
15. Type B thermocouples are suitable for:
About this Quiz
15 multiple choice questions on temperature measurement, the kind asked in instrumentation interviews, technician exams and plant training. Each answer comes with a short explanation, so the quiz works as a revision sheet too.
Show answer key
- 100 Ω at 0 °C: Pt100: 100 Ω at 0 °C (IEC 60751).
- 138.5 Ω: 138.51 Ω.
- Type K: Type K, NiCr/NiAl.
- Compensate for lead resistance: The third wire lets the transmitter cancel lead resistance.
- Thermocouples: A thermocouple measures the difference between hot and cold junctions.
- Red: ANSI makes the negative conductor red for all types.
- Green: IEC type K: green positive, white negative.
- Read the temperature at the short: The short forms a new junction at that point.
- Better accuracy and stability below about 600 °C: RTDs are more accurate and stable in their range.
- Protect the sensor and allow removal without process shutdown: The well keeps the process sealed when the sensor is removed.
- ± 0.35 °C: ± (0.15 + 0.002 × 100) = ± 0.35 °C.
- 212 °F: 100 × 9/5 + 32 = 212 °F.
- ASME PTC 19.3 TW: ASME PTC 19.3 TW covers thermowell design and wake frequency.
- Output on sensor failure (upscale or downscale): It sets whether a broken sensor drives the output high or low.
- Very high temperatures up to about 1700 °C: Type B (Pt30Rh/Pt6Rh) is used from about 600 to 1700 °C.
Frequently Asked Questions
Is this quiz free?
Yes. No sign up is needed and you can retake it as often as you like.
Are the answers explained?
Yes. After you check your answers, each question shows the correct answer and a short explanation.