Free engineering calculators and unit convertersceo@instrumentationblog.in
Flow and Control Valves · Free Excel Calculator

DP Flow Transmitter Rerange Calculator

When a flow loop needs a new maximum flow, this sheet calculates the new DP range for the same orifice, checks it against the transmitter URL and builds a flow, DP and mA table.

Excel (.xlsx)Worked exampleWorks offlineFree, no sign up

Download

  • Calculator sheet with a worked example
  • How to Use sheet with steps
  • 58 built in formulas, no macros
  • Yellow input cells, grey results
  • Calculation sign off block
  • Excel, Google Sheets and LibreOffice

Worked Example

These are the results of the example already filled in the workbook. Replace the yellow cells with your own data.

Present maximum flow40
Present DP at maximum (mbar)250
New maximum flow50
Transmitter URL (mbar)620
New DP at maximum (mbar)390.6
URL checkOK, within URL
Turndown on sensor (URL ÷ span)1.6

New range table

Flow (% of new max)FlowDP (mbar)DP (% of span)mA (linear transmitter)mA (square root transmitter)Notes
00.000.000.04.0004.000
105.003.911.04.1605.600
2010.0015.624.04.6407.200
3015.0035.169.05.4408.800
4020.0062.5016.06.56010.400
5025.0097.6625.08.00012.000
6030.00140.6236.09.76013.600
7035.00191.4149.011.84015.200
8040.00250.0064.014.24016.800
9045.00316.4181.016.96018.400
10050.00390.62100.020.00020.000
Advertisement

About this Calculator

Plant capacity changes often require reranging DP flow loops. This sheet does the square law calculation, checks the transmitter can still measure the new range and produces a test table.

Basis: For a fixed orifice and fluid, DP ∝ Q²: DP_new = DP_old × (Q_new ÷ Q_old)². Flow % = √(DP %). Coefficient changes with Reynolds number are neglected; resize the orifice for large changes.

How to use

  1. Enter present maximum flow and DP.
  2. Enter the new maximum flow and transmitter URL.
  3. Read the new DP span and URL check.
  4. Use the table to set and test the transmitter.
  5. Update all related documents and settings.

Formulas used

  • DP_new = DP_old × (Q_new ÷ Q_old)².
  • DP % = (flow %)².
  • mA linear = 4 + 16 × DP %; mA square root = 4 + 16 × flow %.

Related tools

Advertisement

Frequently Asked Questions

Can I rerange without a new orifice?

If the new DP stays within the transmitter URL and a sensible DP range, yes.

Why is turndown important?

A small span on a large URL sensor reduces accuracy.

What else must change?

DCS scaling, totaliser, alarms and documentation.