DP Flow Square Root Scaling Table

Convert between DP and flow for any DP flowmeter. The workbook builds a table from 0 to 100 % flow with the matching DP and transmitter output in linear and square root modes, and converts a live DP reading to flow.

Excel (.xlsx)Worked exampleWorks offlineFree, no sign up

Download

  • Calculator sheet with a worked example
  • How to Use sheet with steps
  • 129 built in formulas, no macros
  • Yellow input cells, grey results
  • Calculation sign off block
  • Excel, Google Sheets and LibreOffice

Worked Example

These are the results of the example already filled in the workbook. Replace the yellow cells with your own data.

Maximum flow120
Flow unitm³/h
DP at maximum flow (mbar)250
Low flow cut off (% flow)6
Measured DP (mbar)62.5
Flow at measured DP60.00
Flow (%)50.0
mA (square root output)12.000

Flow, DP and output

Flow (%)FlowDP (mbar)DP (%)mA, linear DP outputmA, square root outputCut off
00.000.000.004.0004.000Below cut off
56.000.620.254.0404.800Below cut off
1012.002.501.004.1605.600
1518.005.622.254.3606.400
2024.0010.004.004.6407.200
2530.0015.626.255.0008.000
3036.0022.509.005.4408.800
3542.0030.6212.255.9609.600
4048.0040.0016.006.56010.400
4554.0050.6220.257.24011.200
5060.0062.5025.008.00012.000
5566.0075.6230.258.84012.800

… and 9 more rows in the download.

Advertisement

About this Calculator

DP flowmeters measure the square of flow, which confuses operators and catches out commissioning teams: half flow is only a quarter of the DP. A clear table of flow, DP and mA in both output modes avoids double square root errors and makes calibration quick.

Basis: Square law of DP flow elements: Q ÷ Qmax = √(ΔP ÷ ΔPmax).

How to use

  1. Enter the maximum flow, the DP at that flow and a low flow cut off.
  2. Use the table for calibration and for checking DCS readings.
  3. Type a measured DP into the live conversion to get the flow instantly.
  4. Remember: take the square root in the transmitter or in the DCS, not both.

Formulas used

  • DP = DPmax × (Q ÷ Qmax)².
  • Q = Qmax × √(DP ÷ DPmax).
  • Linear DP output: mA = 4 + 16 × DP%; square root output: mA = 4 + 16 × flow%.

Related tools

Advertisement

Frequently Asked Questions

Why is 50 % flow only 25 % DP?

DP is proportional to flow squared, and 0.5² = 0.25.

Should square root be done in the transmitter or the DCS?

Either, but only once. Doing it in both gives a wildly wrong reading.

Why use a low flow cut off?

Near zero the square root amplifies noise; a cut off forces the reading to zero below a few % of flow.