Layers of Protection Analysis (LOPA) Worksheet
Work through LOPA scenarios: initiating event frequency, independent protection layers and conditional modifiers give the mitigated frequency, the gap to the tolerable frequency and the SIL target for the SIF.
Download
- Calculator sheet with a worked example
- How to Use sheet with steps
- 36 built in formulas, no macros
- Yellow input cells, grey results
- Calculation sign off block
- Excel, Google Sheets and LibreOffice
Worked Example
These are the results of the example already filled in the workbook. Replace the yellow cells with your own data.
Scenarios (frequencies per year)
| Scenario | Initiating event | IE freq | IPL 1 PFD | IPL 2 PFD | IPL 3 PFD | Modifiers | Mitigated freq | Tolerable freq | Required RRF | SIF target | Remarks |
|---|---|---|---|---|---|---|---|---|---|---|---|
| High pressure in V 101, blocked outlet | Control valve fails closed | 2.00 × 10⁻¹ | 1.00 × 10⁻¹ | 1.00 × 10⁻¹ | 1.00 | 2.00 × 10⁻³ | 1.00 × 10⁻⁵ | 200 | SIL 2 | ||
| Tank overfill | Level control failure | 1.00 × 10⁻¹ | 1.00 × 10⁻¹ | 0.50 | 5.00 × 10⁻³ | 1.00 × 10⁻⁴ | 50 | SIL 1 | |||
| Fuel gas explosion in furnace on start up | Purge failure | 2.00 × 10⁻¹ | 1.00 × 10⁻¹ | 0.30 | 6.00 × 10⁻³ | 1.00 × 10⁻⁵ | 600 | SIL 2 |
About this Calculator
LOPA turns HAZOP scenarios into a SIL target with a transparent calculation. A consistent worksheet makes reviews faster and decisions traceable.
Basis: Mitigated frequency = initiating frequency × Π PFD of IPLs × conditional modifiers. Required RRF = mitigated ÷ tolerable. SIL bands per IEC 61511 (low demand).
How to use
- Take scenarios from the HAZOP.
- Enter initiating event frequency per year.
- Enter PFD of each credited IPL and any conditional modifiers.
- Enter the tolerable frequency from your risk criteria.
- Read mitigated frequency, required RRF and SIL target.
Formulas used
- Mitigated = IE × PFD1 × PFD2 × PFD3 × modifiers.
- RRF = mitigated ÷ tolerable.
- SIL 1: 10 to 100, SIL 2: 100 to 1000, SIL 3: 1000 to 10,000.
Related tools
Frequently Asked Questions
What is a conditional modifier?
A probability such as occupancy or ignition that reduces the chance of the consequence.
Can an alarm be an IPL?
Yes, with enough time to respond and an independent sensor; often PFD 0.1.
What if RRF exceeds 10,000?
Redesign the process or add non instrumented layers rather than relying on SIL 4.