Alarm Rationalisation and Priority Worksheet

Rationalise alarms with a simple priority matrix: consequence severity and allowable response time set the priority. The sheet checks the priority distribution against the common 80, 15, 5 % guideline.

Excel (.xlsx)Worked exampleWorks offlineFree, no sign up

Download

  • Calculator sheet with a worked example
  • How to Use sheet with steps
  • 84 built in formulas, no macros
  • Yellow input cells, grey results
  • Calculation sign off block
  • Excel, Google Sheets and LibreOffice

Worked Example

These are the results of the example already filled in the workbook. Replace the yellow cells with your own data.

UnitBoiler 3
Alarm philosophyAPH 001 rev 2
TeamOperations, process, instrument

Alarms

Alarm tagDescriptionSeverityTime to respondScorePriorityOperator actionKeep?Set pointRemarks
PAHH 1101Steam header very high pressureSevereUnder 5 min6HighKeep
LAL 2101Drum level lowSevere5 to 15 min5HighKeep
TAH 3105Bearing temperature highMajor5 to 15 min4MediumKeep
FAL 4102Cooling water flow lowMajor15 to 30 min3LowKeep
PAL 5101Instrument air pressure lowMajorUnder 5 min5HighKeep
AAH 6101Effluent pH highMinor15 to 30 min2LowKeep
LAH 7101Day tank level highMinor5 to 15 min3LowKeep
High priority (%):43  ·  Medium priority (%):14  ·  Low priority (%):43  ·  Alarms marked for removal:0
Advertisement

About this Calculator

Too many alarms, or too many high priority ones, hide the important ones. Rationalisation gives each alarm a purpose, an action and a justified priority.

Basis: Example priority matrix (edit to your alarm philosophy): High when severity and urgency together score 5 or more, Medium at 4, Low otherwise. Distribution guidance about 80 % low, 15 % medium, 5 % high (ISA 18.2 / EEMUA 191).

How to use

  1. List alarms from the DCS.
  2. For each, agree the worst consequence without operator action and the time available.
  3. Priority is calculated; adjust the matrix to your philosophy if needed.
  4. Record the operator action and decide keep, remove or change.
  5. Compare the distribution with the guideline.

Formulas used

  • Score = severity rank (1 to 3) + urgency rank (1 to 3).
  • High ≥ 5, Medium = 4, Low ≤ 3.
  • Distribution = count per priority ÷ total.

Related tools

Advertisement

Frequently Asked Questions

What distribution is recommended?

About 80 % low, 15 % medium and 5 % high is common guidance.

What is an alarm without action?

A nuisance; convert it to an event or remove it.

Is the matrix standard?

No, each site defines its own in the alarm philosophy; this is an editable example.