Cable Voltage Drop and Size Selection Calculator

Find the smallest copper or aluminium cable that keeps the voltage drop within your limit. The workbook calculates the drop for every standard size from 1.5 to 300 mm² at the conductor operating temperature.

Excel (.xlsx)Worked exampleWorks offlineFree, no sign up

Download

  • Calculator sheet with a worked example
  • How to Use sheet with steps
  • 66 built in formulas, no macros
  • Yellow input cells, grey results
  • Calculation sign off block
  • Excel, Google Sheets and LibreOffice

Worked Example

These are the results of the example already filled in the workbook. Replace the yellow cells with your own data.

SystemThree phase
Voltage (V, line to line for 3 phase)415
Load current (A)45
Power factor0.85
Route length, one way (m)120
ConductorCopper
Conductor temperature (°C)70
Allowed voltage drop (%)3
Reactance (Ω/km)0.08

Voltage drop for each size

Size (mm²)Copper R20 (Ω/km)Aluminium R20 (Ω/km)R at temperature (Ω/km)Voltage drop (V)Voltage drop (%)Within limit
1.512.114.4777115.4927.83CHECK
2.57.418.866170.8817.08CHECK
44.615.515944.2510.66CHECK
63.083.685229.697.15CHECK
101.832.189617.804.29CHECK
161.151.911.376011.332.73OK
250.7271.20.86997.311.76OK
350.5240.8680.62705.381.30OK
500.3870.6410.46304.080.98OK
700.2680.4430.32072.940.71OK
950.1930.320.23092.230.54OK
1200.1530.2530.18311.850.45OK

… and 4 more rows in the download.

Smallest size within the voltage drop limit (mm²):16  ·  Voltage drop with that size (%):2.73
Advertisement

About this Calculator

Long motor and instrument power feeders are usually sized by voltage drop rather than current. Seeing the drop for every standard size side by side makes it easy to choose and justify the cable, and to see what one size up or down would mean.

Basis: Conductor resistances from IEC 60228 (class 2, at 20 °C), corrected to operating temperature. Current carrying capacity is not checked: confirm it with IEC 60364-5-52 or your cable data.

How to use

  1. Select the system and enter voltage, current, power factor and route length.
  2. Choose copper or aluminium and the conductor operating temperature (70 °C PVC, 90 °C XLPE).
  3. Set the allowed voltage drop (often 3 % for lighting and 5 % for power, per project).
  4. Read the smallest size within the limit, then confirm its current rating for your installation method.

Formulas used

  • R at temperature = R20 × (1 + α (T − 20)), α = 0.00393 (Cu) or 0.00403 (Al).
  • ΔV = k × I × L × (R cos φ + X sin φ) ÷ 1000.
  • Smallest size = first row with ΔV % within the limit (INDEX and MATCH).

Related tools

Advertisement

Frequently Asked Questions

What voltage drop is allowed in a cable?

Many standards and projects allow 3 % for lighting and 5 % for other loads from the origin of the installation, but check your local rules.

Why use resistance at operating temperature?

Copper resistance rises about 0.39 % per °C, so a cable at 70 °C has about 20 % more resistance than at 20 °C.

Does this sheet check current capacity?

No. Confirm the current rating for your installation method and grouping from IEC 60364-5-52 or the cable manufacturer.