Free engineering calculators and unit convertersceo@instrumentationblog.in
Electrical · Free Excel Calculator

UPS and Battery Sizing for Control Systems

List the loads on a control system UPS. The sheet totals the load, sizes the UPS kVA with margin and calculates the battery capacity for the required backup time.

Excel (.xlsx)Worked exampleWorks offlineFree, no sign up

Download

  • Calculator sheet with a worked example
  • How to Use sheet with steps
  • 19 built in formulas, no macros
  • Yellow input cells, grey results
  • Calculation sign off block
  • Excel, Google Sheets and LibreOffice

Worked Example

These are the results of the example already filled in the workbook. Replace the yellow cells with your own data.

Load power factor0.9
Design margin (%)25
Backup time (h)1
Battery bank voltage (V DC)192
Inverter efficiency (0 to 1)0.9
Ageing factor1.25
Usable depth of discharge (0 to 1)0.8

UPS loads

NoLoadQtyPower each (W)Total (W)Critical?Remarks
1DCS controller cabinets26001,200Yes
2SIS cabinet1500500Yes
3Operator stations33501,050Yes
4Network switches460240Yes
5Field 24 V DC supplies2480960Yes
Total load (W):3,950  ·  UPS rating with margin (kVA):5.5  ·  Battery capacity required (Ah):36  ·  Battery energy (kWh):6.9
Advertisement

About this Calculator

Control systems must ride through power failures long enough to shut down safely or switch to backup power. This sheet gives a documented first estimate of UPS and battery size.

Basis: UPS kVA = Σ W ÷ PF × (1 + margin). Battery Ah = P × t ÷ (Vdc × η) × ageing factor ÷ depth of discharge. Simplified constant power method; final sizing per battery maker discharge tables (for example IEEE 485 approach).

How to use

  1. List all loads fed by the UPS.
  2. Set power factor, margin and backup time.
  3. Enter battery voltage, inverter efficiency, ageing and depth of discharge.
  4. Read UPS kVA and battery Ah.
  5. Confirm with vendor discharge data.

Formulas used

  • kVA = ΣW ÷ PF × (1 + margin) ÷ 1000.
  • Ah = ΣW × t ÷ (Vdc × η) × ageing ÷ DoD.

Related tools

Advertisement

Frequently Asked Questions

What ageing factor is usual?

1.25 is common, so a battery still meets the load at 80 % capacity at end of life.

Why depth of discharge?

Deep discharge shortens battery life; limiting it keeps the battery healthy.

Does temperature matter?

Yes, cold reduces capacity; apply a temperature factor from the maker.