Alarm and Trip Set Point List Template

The master list of alarm and trip set points. Enter LL, L, H and HH values with range, priority and action; the sheet checks that set points are in order and inside the instrument range.

Excel (.xlsx)Printable PDFFilled exampleFree, no sign up

Download

  • How to Use sheet with steps
  • Template sheet, blank and ready
  • Example sheet, filled in
  • 104 built in formulas
  • A4 landscape print setup
  • Works in Excel, Google Sheets and LibreOffice

Preview of the Filled Example

This is the Example sheet from the download, so you can see exactly how the completed alarm and trip set point list looks.

Plant / unitUtilities, unit 100
RevisionC
Date12 Oct 2026
ReferenceAlarm philosophy AP 001

Set point list

TagDescriptionUnitRange minRange maxLLLHHHTrip systemAction on trip / alarmPriorityDeadbandDelay (s)Set point checkRemarks
PT 1101Steam header pressurebar g01641314.5SISHH: trip burner fuel valvesCritical0.22OK
TT 2101Reactor jacket outlet temperature°C0200150165DCSHH: close steam valve TV 2101High15OK
LT 4102Storage tank levelm0120.81.510.511.2SISHH: close XV 4101; LL: stop pump P 401Critical0.053OK
FT 3101Feed flowm³/h01201595NoneOperator actionMedium210OK
PDT 3105Filter differential pressurembar0500350300NoneChange filterLow1030CHECKExample of an error: HH below H
Rows with set point errors:1  ·  SIS trips listed:2
Advertisement

About the Alarm and Trip Set Point List

Alarm and trip set points are among the most safety critical data in a plant, yet they are often scattered across P&IDs, DCS configuration and SIS documents. One controlled list, reviewed by process, instrumentation and operations, keeps them consistent and is the reference for configuration, loop checks and management of change.

How to fill in this template

  1. List every alarm and trip from the cause and effect, P&IDs and alarm philosophy.
  2. Enter the instrument range so set points can be checked against it.
  3. Fill LL, L, H and HH (leave empty if not used), the trip system and the action.
  4. Set priority, deadband and delay according to your alarm philosophy (for example EEMUA 191 or ISA 18.2).
  5. Fix every row that shows CHECK, then issue the list for configuration and loop checks.

What the formulas do

  • Set point check is OK when LL < L < H < HH (ignoring empty values) and all values lie within the range.
  • Counts of rows needing correction and of SIS trips.

Related tools

Advertisement

Frequently Asked Questions

What is the difference between an alarm and a trip?

An alarm asks the operator to act; a trip makes the control or safety system act automatically, for example closing a valve or stopping a pump.

Why add deadband and delay?

They stop nuisance alarms from noisy signals chattering around the set point.

Who approves alarm and trip set points?

Normally process, instrumentation and operations together, and changes go through management of change.

You May Also Like

Learn more on the blog

Types of alarms in DCS every instrumentation engineer should know

A practical guide on instrumentationblog.in that explains the procedure behind this template and how engineers apply it on real plants.

Read Full Article

More Engineering Documents Templates

All Templates and Downloads