VFD Fault Finder (Vendor Neutral)

Choose the type of drive trip and get the usual causes, checks and fixes. Use your drive manual for exact fault codes.

OvercurrentOvervoltageOvertemperatureEarth fault
SymptomOvercurrent trip
Most likely causeAcceleration too fast
First checkTrips during start

Causes in order of likelihood

CauseHow to checkFix
Acceleration too fastTrips during startIncrease acceleration time
Motor or cable shortMegger motor and cable disconnectedRepair insulation
Mechanical jam or overloadTurn the load by handClear the jam
Advertisement

Before You Start

  • Isolate and wait for the DC bus to discharge before touching terminals; verify with a meter.
  • Read the fault history and operating values at the trip.
  • Never megger with the drive connected; disconnect motor cables first.

VFD Fault Finder (Vendor Neutral): All Symptoms

Overcurrent trip

Likely causeHow to checkFix
Acceleration too fastTrips during startIncrease acceleration time
Motor or cable shortMegger motor and cable disconnectedRepair insulation
Mechanical jam or overloadTurn the load by handClear the jam

Overvoltage trip

Likely causeHow to checkFix
Deceleration too fastTrips when stoppingIncrease deceleration time
Overhauling loadLoad drives the motorAdd braking resistor or regeneration
High supply voltageMeasure supplyCorrect supply

Undervoltage trip

Likely causeHow to checkFix
Supply dipsCheck supply eventsRide through settings; supply fix
Loose input connection or blown fuseCheck input terminals and fusesRepair
Failed rectifier or prechargeMaker diagnosticsRepair drive

Overtemperature

Likely causeHow to checkFix
Blocked fan or filterInspect coolingClean or replace fan
High ambientMeasure panel temperatureImprove ventilation
Overload or high switching frequencyCheck current and settingsReduce load or frequency

Earth fault

Likely causeHow to checkFix
Damaged motor cableMegger cable disconnectedReplace cable
Moisture in motorMegger motorDry and test motor
Long cable capacitanceCheck cable lengthOutput reactor or filter

Motor overload

Likely causeHow to checkFix
Load too highCompare current with ratingReduce load
Wrong motor data in driveCheck nameplate parametersCorrect parameters
Low speed self cooled motorLong running at low speedForced cooling or derate
Key insight: note when the trip happens: during acceleration points to overcurrent settings, during deceleration to overvoltage, at steady speed to load or cooling.
Advertisement

Frequently Asked Questions

Why does my drive trip when stopping?

Usually deceleration is too fast for the load inertia.

Can I megger a motor through the drive?

No, disconnect the motor cable from the drive first.

Why are fault codes different between drives?

Each maker uses its own codes; causes by trip type are similar.