PLC Analog Input Fault Finder

Choose the PLC or DCS analog input symptom and get likely causes in scaling, wiring, grounding and module configuration.

Wrong scalingOverrangeNoisyStuck value
SymptomValue wrong but mA correct
Most likely causeScaling or raw range wrong
First checkCompare raw count with expected for the mA

Causes in order of likelihood

CauseHow to checkFix
Scaling or raw range wrongCompare raw count with expected for the mACorrect raw min and max and LRV, URV
Square root applied twiceCheck transmitter and programRemove one
Wrong units or decimal shiftCheck HMI and tag configurationCorrect units
Advertisement

Before You Start

  • Work under a permit, inform the control room and put the loop in manual or bypass the trip before touching a live instrument.
  • Measure the loop current at the input terminals.
  • Read the raw count in the PLC and compare with the expected count.
  • Check module diagnostics and forced values.

PLC Analog Input Fault Finder: All Symptoms

Value wrong but mA correct

Likely causeHow to checkFix
Scaling or raw range wrongCompare raw count with expected for the mACorrect raw min and max and LRV, URV
Square root applied twiceCheck transmitter and programRemove one
Wrong units or decimal shiftCheck HMI and tag configurationCorrect units

Overrange or underrange

Likely causeHow to checkFix
Open wire or fuseMeasure currentRepair wiring
Transmitter in fault currentCheck transmitter statusRepair transmitter
Card range set to 0 to 20 mA or voltageCheck module configurationSet 4 to 20 mA

Noisy value

Likely causeHow to checkFix
Shield earthed at both endsCheck shield terminationsEarth at one end
Cable near VFD or power cablesCheck routingSegregate; use screened cable
No input filteringCheck filter settingsAdd small filter

Channels affect each other

Likely causeHow to checkFix
Mixed 2 and 4 wire devices on shared commonCheck wiring against card manualRewire or use isolators
Ground loop through grounded sensorsLift one ground temporarilyUse isolators
Overloaded loop supplyMeasure supply under loadUpgrade supply

Value stuck

Likely causeHow to checkFix
Forced value in PLCCheck forcesRemove force
Module or channel faultModule diagnosticsReplace module
Transmitter in fixed current modeCheck HARTReturn to normal mode
Key insight: measure the mA first: if the current is right, the problem is in the PLC; if it is wrong, it is in the field.
Advertisement

Frequently Asked Questions

What raw range does Siemens S7 use?

0 to 27648 for 0 to 100 % of a 4 to 20 mA input.

Can I mix 2 and 4 wire transmitters?

Only as the card manual allows.

Where should the shield be earthed?

Usually at the control system end only.