Gas Detector Fault Finder

Choose what the gas detector is doing and get likely causes for catalytic, infrared and electrochemical detectors, with checks and fixes.

Fails bump testZero driftFalse alarmsOptics fault
SymptomReads low on bump test
Most likely causeCatalytic sensor poisoned (silicones, sulfur, lead)
First checkLow response after cleaning

Causes in order of likelihood

CauseHow to checkFix
Catalytic sensor poisoned (silicones, sulfur, lead)Low response after cleaningReplace sensor; find source of poisons
Blocked sinter or weather guardInspect and cleanClean or replace guard
Wrong test gas or flowCheck cylinder and regulatorUse correct gas and flow
Advertisement

Before You Start

  • Work under a permit, inform the control room and put the loop in manual or bypass the trip before touching a live instrument.
  • Inhibit the detector with operations approval and keep the inhibit time short.
  • Use in date, certified test gas of the correct type.
  • Check the sensor installation date against its service life.

Gas Detector Fault Finder: All Symptoms

Reads low on bump test

Likely causeHow to checkFix
Catalytic sensor poisoned (silicones, sulfur, lead)Low response after cleaningReplace sensor; find source of poisons
Blocked sinter or weather guardInspect and cleanClean or replace guard
Wrong test gas or flowCheck cylinder and regulatorUse correct gas and flow

Zero drifts or reads negative

Likely causeHow to checkFix
Zeroed in contaminated airZero with zero gasRezero correctly
Sensor ageingDrift increasing over timeReplace sensor
Temperature or humidity swingsCorrelate with weatherCheck compensation; fit guard

False alarms

Likely causeHow to checkFix
Cross sensitive gases or vapoursCheck process activities nearbyRelocate or choose different sensor
Steam or water on sensorCheck environmentFit splash guard
Radio interferenceAlarm when radios used nearbyImprove shielding; keep radios away

IR optics or beam fault

Likely causeHow to checkFix
Dirty or wet opticsInspect windowsClean; fit hood
Open path misalignedCheck alignment signalRealign
Heavy fog or obstructionCheck pathAccept temporary loss or relocate

No signal in control system

Likely causeHow to checkFix
Inhibit left onCheck fire and gas system statusRemove inhibit
Loop or power faultMeasure currentRepair wiring or supply
Detector fault outputCheck detector statusRepair or replace
Key insight: a bump test proves the detector sees gas; only a calibration proves it reads the right amount.
Advertisement

Frequently Asked Questions

How often should detectors be bump tested?

As set by the site and maker; often monthly to quarterly for fixed detectors, with calibration at longer intervals.

Why do catalytic sensors fail low?

Poisoning or inhibition reduces their response, which is dangerous.

Can IR detect hydrogen?

No; hydrogen needs catalytic, electrochemical or other sensor types.