Guided Wave Radar Fault Finder

Choose what the GWR transmitter shows and get the likely causes, with checks on the echo curve and the fixes.

Lost echoEnd of probeInterface wrongCoating
SymptomReads end of probe or empty when not
Most likely causeDielectric too low for probe type
First checkWeak level peak on echo curve

Causes in order of likelihood

CauseHow to checkFix
Dielectric too low for probe typeWeak level peak on echo curveUse coaxial or single lead in chamber; adjust thresholds
Wrong probe length settingCompare with measured probeCorrect length
Probe disconnected or brokenNo reference pulseRepair or replace probe
Advertisement

Before You Start

  • Work under a permit, inform the control room and put the loop in manual or bypass the trip before touching a live instrument.
  • Save the echo curve before changing anything.
  • Check probe type, length, reference point and dielectric settings.
  • Compare with a gauge glass or manual dip.

Guided Wave Radar Fault Finder: All Symptoms

Reads end of probe or empty when not

Likely causeHow to checkFix
Dielectric too low for probe typeWeak level peak on echo curveUse coaxial or single lead in chamber; adjust thresholds
Wrong probe length settingCompare with measured probeCorrect length
Probe disconnected or brokenNo reference pulseRepair or replace probe

Reads full or near top

Likely causeHow to checkFix
Condensation or buildup at nozzlePeak near top on echo curveClean; adjust upper blocking or threshold
Probe touching nozzle wallInspect installationCentre probe; use larger nozzle
Level truly in upper dead zoneCompare with gaugeReconfigure range

Interface level wrong

Likely causeHow to checkFix
Wrong upper liquid dielectricCheck settingsEnter correct dielectric
Emulsion layerSample at several heightsAccept emulsion or use other technology
Upper layer too thinCheck minimum layer thicknessAccept limit or change method

Reading jumps

Likely causeHow to checkFix
Coating along probeMultiple peaks on echo curveClean probe; choose coated probe type
Turbulence or foam in vesselCorrelates with agitator or fillingUse stilling well or chamber
Interference from chamber inletsPeaks at nozzle heightsAdjust thresholds; centring disc
Key insight: the echo curve is the truth: save it at commissioning and compare whenever the reading looks wrong.
Advertisement

Frequently Asked Questions

Can GWR measure interface?

Yes, if the upper liquid has a lower dielectric and the layers are clear.

Why does coating matter?

Buildup along the probe creates echoes and can mask the real level.

Is GWR affected by density?

Not for total level, which is a major advantage over DP and displacers.