Choose what the vortex meter shows and get likely causes, checks and fixes for steam, gas and liquid service.

Zero at low flowFalse flowReads lowUnstable
SymptomReads zero at low flow
Most likely causeBelow minimum velocity or Reynolds number
First checkCompare velocity with meter limits

Causes in order of likelihood

CauseHow to checkFix
Below minimum velocity or Reynolds numberCompare velocity with meter limitsUse a smaller meter or another technology
Low flow cutoff set highCheck cutoff settingLower within maker limits
Trigger level too highCheck signal amplitude settingsAdjust per manual
Advertisement

Before You Start

  • Work under a permit, inform the control room and put the loop in manual or bypass the trip before touching a live instrument.
  • Check K factor, pipe ID, units and density basis against the certificate.
  • Note normal velocity and compare with the meter minimum.
  • Look for vibration sources near the meter.

Vortex Flowmeter Fault Finder: All Symptoms

Reads zero at low flow

Likely causeHow to checkFix
Below minimum velocity or Reynolds numberCompare velocity with meter limitsUse a smaller meter or another technology
Low flow cutoff set highCheck cutoff settingLower within maker limits
Trigger level too highCheck signal amplitude settingsAdjust per manual

Shows flow with no flow

Likely causeHow to checkFix
Pipe vibration counted as vorticesReading changes with pumps on or offRaise filter or trigger; improve supports
Valve passingIsolate both sidesRepair the valve
Electrical noiseCheck grounding and cable routingCorrect grounding; segregate cables

Reads low

Likely causeHow to checkFix
Wrong K factor or pipe IDCompare configuration with certificateCorrect configuration
Two phase flow or wet steamCheck steam quality and trapsImprove separation and trapping
Short straight run or swirlCheck upstream fittingsAdd straight run or conditioner

Reads high

Likely causeHow to checkFix
Pulsation adds countsCheck pumps and compressorsMove meter or dampen pulsation
Density basis wrong for mass flowCheck pressure and temperature compensationCorrect the density source
Wrong unitsCheck units and totaliserCorrect settings

Unstable reading

Likely causeHow to checkFix
Flow near minimum velocityCompare with limitsResize meter
Swirl from double bendsCheck piping layoutAdd conditioner
Gasket protruding into flowInspect at shutdownCorrect gasket centring
Key insight: a vortex meter counts pulses, so anything that makes pulses (vibration, pulsation) reads as flow, and anything too slow to shed vortices reads zero.
Advertisement

Frequently Asked Questions

Why does my vortex meter read zero at low flow?

Below its minimum Reynolds number vortices are unstable, so it cuts off.

Can vibration cause false flow?

Yes, near the shedding frequency it can be counted.

Are vortex meters good for steam?

Yes, they are widely used for steam with pressure and temperature compensation.