Cheat Sheets · Free PDF
ISA Instrument Letter Codes Cheat Sheet
The complete ISA 5.1 identification letter table on one printable page, with the most common instrument tag combinations explained.
One page A4Print ready PDFFree, no sign up
Download
A one page A4 sheet to print, pin up in the workshop or keep on your phone. Everything on it is also shown below.
Download PDF A4 · 53 KBISA 5.1 identification letters
| Letter | First letter: variable | Modifier | Readout / passive | Output | Modifier |
|---|---|---|---|---|---|
| A | Analysis | Alarm | |||
| B | Burner, combustion | User’s choice | User’s choice | User’s choice | |
| C | User’s choice (often conductivity) | Control | |||
| D | User’s choice (often density) | Differential | |||
| E | Voltage | Sensor, primary element | |||
| F | Flow, flow rate | Ratio | |||
| G | User’s choice | Glass, gauge, viewing device | |||
| H | Hand | High | |||
| I | Current (electrical) | Indicate | |||
| J | Power | Scan | |||
| K | Time, schedule | Time rate of change | Control station | ||
| L | Level | Light | Low | ||
| M | User’s choice (often moisture) | Middle, intermediate | |||
| N | User’s choice | User’s choice | User’s choice | User’s choice | |
| O | User’s choice | Orifice, restriction | |||
| P | Pressure | Point (test) connection | |||
| Q | Quantity | Integrate, totalize | |||
| R | Radiation | Record | |||
| S | Speed, frequency | Safety | Switch | ||
| T | Temperature | Transmit | |||
| U | Multivariable | Multifunction | Multifunction | ||
| V | Vibration, mechanical analysis | Valve, damper, louver | |||
| W | Weight, force | Well | |||
| X | Unclassified | X axis | Unclassified | Unclassified | Unclassified |
| Y | Event, state, presence | Y axis | Relay, compute, convert | ||
| Z | Position, dimension | Z axis | Driver, actuator, final element |
Common tags
| Tag | Meaning |
|---|---|
| PT | Pressure transmitter |
| PDT | Pressure differential transmitter |
| FIC | Flow indicating controller |
| TE / TT | Temperature element / transmitter |
| LSHH | Level switch high high |
| FCV / FV | Flow control valve |
| XV | On/off (shutdown) valve |
| PSV | Pressure safety valve |
| ZSO / ZSC | Position switch open / closed |
| HS | Hand switch |
Reading a tag
- First letter = measured or initiating variable
- Optional modifier (D differential, F ratio, Q totalise)
- Succeeding letters = functions (I indicate, C control, T transmit, A alarm)
- Loop number follows, for example FIC 101 in loop 101
Advertisement
Related Calculators and Tools
Advertisement
Frequently Asked Questions
What does FIC stand for?
Flow indicating controller: F is flow, I indicate, C control.
What is the difference between PT and PI?
PT is a pressure transmitter (sends a signal); PI is a pressure indicator such as a gauge.
What does the letter Z mean?
Position or dimension as the first letter, for example ZSO is a position switch open.
You May Also Like
Learn more on the blog
Instrument index: 10 essential columns
A practical guide on instrumentationblog.in that explains the theory behind this cheat sheet.
Read Full ArticleMore Cheat Sheets
4 to 20 mA Cheat SheetPrintable A4 PDFFlow Measurement Formulas Cheat SheetPrintable A4 PDFPressure Cheat SheetPrintable A4 PDFTemperature Measurement Cheat SheetPrintable A4 PDFLevel Measurement Formulas Cheat SheetPrintable A4 PDFControl Valve Cheat SheetPrintable A4 PDFElectrical Formulas Cheat SheetPrintable A4 PDFOp Amp Formulas Cheat SheetPrintable A4 PDFElectronic Component Codes Cheat SheetPrintable A4 PDFPID Tuning Cheat SheetPrintable A4 PDFIP, NEMA and Ex Rating Cheat SheetPrintable A4 PDF