Control Valve Cheat Sheet

Control valve essentials on one page: Cv and Kv sizing for liquids, choked flow, valve characteristics, sizing rules, leakage classes and fail action terms.

One page A4Print ready PDFFree, no sign up

Download

Control Valve Cheat Sheet PDF preview

A one page A4 sheet to print, pin up in the workshop or keep on your phone. Everything on it is also shown below.

Download PDF A4 · 86 KB

Liquid sizing

Cv (US units)Cv = Q (US gpm) × √(SG ÷ ΔP (psi))
Kv (metric)Kv = Q (m³/h) × √(SG ÷ ΔP (bar))
ConversionCv = 1.156 × Kv, Kv = 0.865 × Cv
Flow from CvQ = Cv × √(ΔP ÷ SG)

Choked flow (IEC 60534)

Maximum useful ΔPΔPmax = FL² × (P1 − FF × Pv)
FF0.96 − 0.28 × √(Pv ÷ Pc)
Cavitation indexσ = (P1 − Pv) ÷ (P1 − P2)

Flow does not increase once ΔP exceeds ΔPmax; expect cavitation or flashing.

Inherent characteristics

TypeBehaviourTypical use
LinearFlow ∝ travelLevel, constant ΔP
Equal %Each step of travel changes flow by the same %Pressure, flow, varying ΔP
Quick openingMost flow in first travelOn/off, relief
Advertisement

Sizing rules of thumb

  • Maximum flow at about 70 to 85 % open; minimum flow above about 10 %
  • Valve authority: valve ΔP at least 25 to 50 % of system ΔP
  • Body often one size smaller than the line; include reducer losses in sizing
  • Check noise (85 dBA at 1 m is a common limit), cavitation and outlet velocity

Seat leakage (ANSI/FCI 70-2)

ClassMaximum leakage
II0.5 % of rated capacity
III0.1 % of rated capacity
IV0.01 % of rated capacity
V5 × 10⁻¹² m³/s water per mm port diameter per bar ΔP
VIBubbles per minute by size, for example 1 at 1", 3 at 2", 11 at 4"

Fail action terms

TermMeaning
ATOAir to open = fail close (FC)
ATCAir to close = fail open (FO)
FL / FAIFail last position / as is
Direct acting positionerIncreasing signal increases output pressure

Rangeability

DefinitionR = Cvmax, controllable ÷ Cvmin, controllable
TypicalGlobe 30:1 to 50:1, ball (V port) 100:1 or more

Common problems

SymptomCheck
HuntingOversized valve, tight packing, tuning
Cannot reach set pointUndersized valve, low supply air
Noise, vibrationCavitation or high gas velocity
Seat leakageDamaged trim, wrong bench set

Related Calculators and Tools

Advertisement

Frequently Asked Questions

What is the difference between Cv and Kv?

Cv is US gallons per minute of water at 1 psi drop; Kv is m³/h at 1 bar drop. Cv = 1.156 Kv.

What leakage class is tight shut off?

Class VI is often called bubble tight; class V is also used for tight metal seated valves.

Is ATO the same as fail close?

Yes. An air to open valve closes on loss of air.