Control Valve Cheat Sheet
Control valve essentials on one page: Cv and Kv sizing for liquids, choked flow, valve characteristics, sizing rules, leakage classes and fail action terms.
One page A4Print ready PDFFree, no sign up
Download
A one page A4 sheet to print, pin up in the workshop or keep on your phone. Everything on it is also shown below.
Download PDF A4 · 86 KBLiquid sizing
| Cv (US units) | Cv = Q (US gpm) × √(SG ÷ ΔP (psi)) |
| Kv (metric) | Kv = Q (m³/h) × √(SG ÷ ΔP (bar)) |
| Conversion | Cv = 1.156 × Kv, Kv = 0.865 × Cv |
| Flow from Cv | Q = Cv × √(ΔP ÷ SG) |
Choked flow (IEC 60534)
| Maximum useful ΔP | ΔPmax = FL² × (P1 − FF × Pv) |
| FF | 0.96 − 0.28 × √(Pv ÷ Pc) |
| Cavitation index | σ = (P1 − Pv) ÷ (P1 − P2) |
Flow does not increase once ΔP exceeds ΔPmax; expect cavitation or flashing.
Inherent characteristics
| Type | Behaviour | Typical use |
|---|---|---|
| Linear | Flow ∝ travel | Level, constant ΔP |
| Equal % | Each step of travel changes flow by the same % | Pressure, flow, varying ΔP |
| Quick opening | Most flow in first travel | On/off, relief |
Advertisement
Sizing rules of thumb
- Maximum flow at about 70 to 85 % open; minimum flow above about 10 %
- Valve authority: valve ΔP at least 25 to 50 % of system ΔP
- Body often one size smaller than the line; include reducer losses in sizing
- Check noise (85 dBA at 1 m is a common limit), cavitation and outlet velocity
Seat leakage (ANSI/FCI 70-2)
| Class | Maximum leakage |
|---|---|
| II | 0.5 % of rated capacity |
| III | 0.1 % of rated capacity |
| IV | 0.01 % of rated capacity |
| V | 5 × 10⁻¹² m³/s water per mm port diameter per bar ΔP |
| VI | Bubbles per minute by size, for example 1 at 1", 3 at 2", 11 at 4" |
Fail action terms
| Term | Meaning |
|---|---|
| ATO | Air to open = fail close (FC) |
| ATC | Air to close = fail open (FO) |
| FL / FAI | Fail last position / as is |
| Direct acting positioner | Increasing signal increases output pressure |
Rangeability
| Definition | R = Cvmax, controllable ÷ Cvmin, controllable |
| Typical | Globe 30:1 to 50:1, ball (V port) 100:1 or more |
Common problems
| Symptom | Check |
|---|---|
| Hunting | Oversized valve, tight packing, tuning |
| Cannot reach set point | Undersized valve, low supply air |
| Noise, vibration | Cavitation or high gas velocity |
| Seat leakage | Damaged trim, wrong bench set |
Related Calculators and Tools
Advertisement
Frequently Asked Questions
What is the difference between Cv and Kv?
Cv is US gallons per minute of water at 1 psi drop; Kv is m³/h at 1 bar drop. Cv = 1.156 Kv.
What leakage class is tight shut off?
Class VI is often called bubble tight; class V is also used for tight metal seated valves.
Is ATO the same as fail close?
Yes. An air to open valve closes on loss of air.
You May Also Like
Learn more on the blog
Control valve flow coefficient (Cv and Kv)
A practical guide on instrumentationblog.in that explains the theory behind this cheat sheet.
Read Full ArticleMore Cheat Sheets
4 to 20 mA Cheat SheetPrintable A4 PDFFlow Measurement Formulas Cheat SheetPrintable A4 PDFPressure Cheat SheetPrintable A4 PDFTemperature Measurement Cheat SheetPrintable A4 PDFLevel Measurement Formulas Cheat SheetPrintable A4 PDFElectrical Formulas Cheat SheetPrintable A4 PDFOp Amp Formulas Cheat SheetPrintable A4 PDFElectronic Component Codes Cheat SheetPrintable A4 PDFPID Tuning Cheat SheetPrintable A4 PDFISA Instrument Letter Codes Cheat SheetPrintable A4 PDFIP, NEMA and Ex Rating Cheat SheetPrintable A4 PDF