IP code: first digit (solids)

DigitProtection
0None
1Objects over 50 mm
2Objects over 12.5 mm (fingers)
3Objects over 2.5 mm
4Objects over 1 mm
5Dust protected
6Dust tight

IP code: second digit (water)

DigitProtection
0None
1Vertically dripping water
2Dripping water, tilted 15°
3Spraying water up to 60°
4Splashing from any direction
5Water jets (6.3 mm nozzle)
6Powerful jets (12.5 mm nozzle)
7Immersion to 1 m, 30 min
8Continuous immersion beyond 1 m (as specified)
9High pressure, high temperature jets

IEC 60529. IP68 conditions are set by the manufacturer.

NEMA types and nearest IP

NEMAUseIP
1IndoorIP10
2IndoorIP11
3Indoor or outdoorIP54
3RIndoor or outdoorIP14
3SIndoor or outdoorIP54
4Indoor or outdoorIP66
4XIndoor or outdoorIP66
5IndoorIP52
6Indoor or outdoorIP67
6PIndoor or outdoorIP68
12IndoorIP52
12KIndoorIP52
13IndoorIP54

NEMA to IP is one way only: a NEMA type meets at least that IP, not the reverse.

Advertisement

Zones and EPL (IEC 60079-10)

ZoneHazard presentEPL
0 / 20Continuously or for long periodsGa / Da
1 / 21Likely in normal operationGb / Db
2 / 22Not likely, short periods onlyGc / Dc

Zones 0, 1, 2 for gas; 20, 21, 22 for dust.

Gas and dust groups

GroupExample
IIAPropane
IIBEthylene
IICHydrogen, acetylene
IIIACombustible flyings
IIIBNon conductive dust
IIICConductive dust

IIC equipment may be used in IIB and IIA areas.

Temperature classes

ClassMax surface °C
T1450
T2300
T3200
T4135
T5100
T685

Ex protection concepts

CodeConceptZones
iaIntrinsic safety0, 1, 2
ibIntrinsic safety1, 2
d (db)Flameproof enclosure1, 2
e (eb)Increased safety1, 2
pPressurised1, 2
mEncapsulation0 to 2 (ma)
ec / nANon sparking2
tDust protection by enclosure21, 22

Example marking

GasEx db IIC T4 Gb
ReadingFlameproof, hydrogen group, max 135 °C, Zone 1
ATEX⟨Ex⟩ II 2 G = group II surface, category 2 (Zone 1), gas

Related Calculators and Tools

Advertisement

Frequently Asked Questions

What does IP67 mean?

Dust tight (6) and protected against temporary immersion to 1 m for 30 minutes (7).

What is the IP equivalent of NEMA 4X?

At least IP66, plus corrosion resistance which IP does not cover.

What does T4 mean on Ex equipment?

The maximum surface temperature is 135 °C, so it is safe for gases with an ignition temperature above 135 °C.