SIL and Functional Safety Cheat Sheet
The key numbers and formulas of IEC 61511 functional safety on one page: SIL bands, PFDavg for common voting, failure fractions, hardware fault tolerance and LOPA.
Download
A one page A4 sheet to print, pin up in the workshop or keep on your phone. Everything on it is also shown below.
Download PDF A4 · 90 KBSIL bands (low demand, IEC 61511)
| SIL | PFDavg | RRF |
|---|---|---|
| 1 | 10⁻² to 10⁻¹ | 10 to 100 |
| 2 | 10⁻³ to 10⁻² | 100 to 1000 |
| 3 | 10⁻⁴ to 10⁻³ | 1000 to 10,000 |
| 4 | 10⁻⁵ to 10⁻⁴ | 10,000 to 100,000 |
High demand (PFH per hour)
| SIL | PFH |
|---|---|
| 1 | 10⁻⁶ to 10⁻⁵ |
| 2 | 10⁻⁷ to 10⁻⁶ |
| 3 | 10⁻⁸ to 10⁻⁷ |
| 4 | 10⁻⁹ to 10⁻⁸ |
High demand: more than one demand per year.
PFDavg (simplified, IEC 61508-6)
| 1oo1 | λDU × TI ÷ 2 |
| 1oo2 | (λDU TI)² ÷ 3 + β λDU TI ÷ 2 |
| 2oo3 | (λDU TI)² + β λDU TI ÷ 2 |
| 2oo2 | λDU × TI |
| RRF | 1 ÷ PFDavg |
| Imperfect test | PTC λDU TI ÷ 2 + (1 − PTC) λDU MT ÷ 2 |
Failure fractions
| Total rate | λ = λSD + λSU + λDD + λDU |
| SFF | (λS + λDD) ÷ λ |
| Diagnostic coverage | λDD ÷ (λDD + λDU) |
| MTBF | 1 ÷ λ |
| 1 FIT | 1 failure per 10⁹ h |
| Spurious trips 1oo1 | STR ≈ λS |
Minimum HFT (IEC 61511 Ed. 2)
| SIL | HFT |
|---|---|
| 1 | 0 |
| 2 (low demand) | 0 |
| 2 (high demand) | 1 |
| 3 | 1 |
| 4 | 2 |
Voting at a glance
| Voting | HFT | Spurious trips |
|---|---|---|
| 1oo1 | 0 | Base |
| 1oo2 | 1 | About double |
| 2oo2 | 0 | Lowest |
| 2oo3 | 1 | Low |
LOPA
| Mitigated frequency | f = fIE × Π PFDIPL × modifiers |
| Required RRF | f ÷ ftolerable |
| Example | 0.2 × 0.1 × 0.1 = 2 × 10⁻³ /yr; target 10⁻⁵ → RRF 200 → SIL 2 |
Typical IPL credits
| Layer | PFD |
|---|---|
| BPCS loop (maximum claim) | 0.1 |
| Operator response to alarm (enough time) | often 0.1 |
| Relief valve | often 0.01 |
| SIF | per SIL |
Use your company LOPA rules; credits must be independent, effective and auditable.
Proof test essentials
- Test interval in the calculation must match real practice.
- Record as found condition before repairs.
- Test final elements fully: stroke, time and tight shut off.
- Bypasses: approved, registered, time limited, with compensating measures.
Related Calculators and Tools
Frequently Asked Questions
What PFDavg does SIL 2 need?
Between 10⁻³ and 10⁻² in low demand mode, which is a risk reduction of 100 to 1000.
Why does β matter so much?
Common cause failures defeat redundancy; with β of a few percent they often dominate 1oo2 PFDavg.
What is HFT 1?
The function still works with one dangerous hardware fault, as in 1oo2 or 2oo3.