PID Tuning Cheat Sheet
PID tuning on one page: Ziegler–Nichols tables, Cohen–Coon, lambda tuning for self regulating and integrating loops, PID algorithm forms and a troubleshooting guide.
Download
A one page A4 sheet to print, pin up in the workshop or keep on your phone. Everything on it is also shown below.
Download PDF A4 · 79 KBZiegler–Nichols closed loop (ultimate gain)
| Mode | Kc | Ti | Td |
|---|---|---|---|
| P | 0.5 Ku | ||
| PI | 0.45 Ku | Pu ÷ 1.2 | |
| PID | 0.6 Ku | Pu ÷ 2 | Pu ÷ 8 |
Ku: gain at sustained oscillation, Pu: its period.
Ziegler–Nichols open loop (step test)
| Mode | Kc | Ti | Td |
|---|---|---|---|
| P | τ ÷ (K θ) | ||
| PI | 0.9 τ ÷ (K θ) | 3.33 θ | |
| PID | 1.2 τ ÷ (K θ) | 2 θ | 0.5 θ |
K: process gain, τ: time constant, θ: dead time.
Lambda tuning (PI)
| Self regulating | Kc = τ ÷ (K (λ + θ)), Ti = τ |
| Integrating (level) | Kc = (2λ + θ) ÷ (K (λ + θ)²), Ti = 2λ + θ |
| Choose λ | τ to 3τ, and at least 3θ for robustness |
Cohen–Coon PID
| Kc | (1 ÷ K)(τ ÷ θ)(4/3 + θ ÷ 4τ) |
| Ti | θ (32 + 6θ/τ) ÷ (13 + 8θ/τ) |
| Td | 4θ ÷ (11 + 2θ/τ) |
PID algorithm forms
| Ideal (ISA) | u = Kc [e + (1 ÷ Ti) ∫e dt + Td de/dt] |
| Parallel | u = Kp e + Ki ∫e dt + Kd de/dt, Ki = Kc ÷ Ti, Kd = Kc × Td |
| Series to ideal | Kc = Kc′ (1 + Td′/Ti′), Ti = Ti′ + Td′, Td = Ti′Td′ ÷ (Ti′ + Td′) |
Units you will meet
| Proportional band | PB % = 100 ÷ Kc |
| Reset rate | repeats/min = 1 ÷ Ti (min) |
| Integral time | min/repeat or s/repeat |
Typical starting values
| Loop | Kc | Ti | Td |
|---|---|---|---|
| Flow | 0.3 to 0.8 | 0.05 to 0.2 min | 0 |
| Liquid pressure | 0.5 to 2 | 0.1 to 0.5 min | 0 |
| Gas pressure | 2 to 10 | 1 to 5 min | 0 |
| Level (averaging) | 1 to 5 | 5 to 20 min | 0 |
| Temperature | 1 to 10 | 2 to 20 min | 0.1 to 2 min |
Starting points only; always tune on the real process.
Troubleshooting
| Symptom | Try |
|---|---|
| Fast oscillation | Lower Kc |
| Slow oscillation | Increase Ti (less integral) |
| Sluggish, offset lasts long | Raise Kc or shorten Ti |
| Noisy output | Reduce Td, filter PV |
| Oscillates at constant amplitude | Check valve stiction first |
Controller action
- Reverse acting: output falls when PV rises (most heating and level outflow loops)
- Direct acting: output rises when PV rises (cooling, level inflow control)
- Wrong action makes the loop run away to a limit
Related Calculators and Tools
Frequently Asked Questions
What are the Ziegler–Nichols PID settings?
Kc = 0.6 Ku, Ti = Pu ÷ 2 and Td = Pu ÷ 8 from the closed loop test.
How do I convert gain to proportional band?
PB % = 100 ÷ Kc. A gain of 2 is a 50 % proportional band.
Which tuning method is most robust?
Lambda tuning, because you choose the closed loop speed directly and it does not aim for an oscillatory response.